| | NOTE: THESE COMMENTS APPLY TO PERMIT NUMBERS 15090189 |
| | AND 15090192 |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE NEW |
| | GARAGE/OFFICE: |
| | A) CLIMATE ZONE ON PAGE 2 OF 4 IS INCORRECT. SEE TABLE |
| | R301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | B) THERE IS NOT KITCHEN. SEC. R103.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | C) CLARIFY WHY THERE IS NOT R-VALUE ON THE FLOOR |
| | INFORMATION ON PAGE 2 OF 4. NEED INSULATION BETWEEN |
| | CONDITIONED SPACE AND UN-CONDITIONED SPACE. |
| | D) THE CEILING R-VALUE ON PAGE 2 OF 4 DOESN'T MATCH |
| | CEILING R-VALUE GIVEN ON PAGE 1 OF 4. |
| | E) INSULATED DOOR SHOWN ON PAGE 3 OF 4 DOESN'T MATCH |
| | PLANS AND PRODUCT APPROVALS SUBMITTED. THIS DOOR NEEDS |
| | TO BE INCLUDED IN GLASS AREA. |
| | F) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T |
| | MATCH PLANS. REVISE GLASS SQUARE FOOTAGE ON EACH |
| | BUILDING ORIENTATION TO MATCH PLANS. AND MISSING |
| | INFORMATION FOR WEST ELEVATION WINDOW. |
| | G) REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS. |
| | H) COMPLETE/CHECK THE AIR BARRIER AND INSULATION |
| | INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 |
| | SUBMITTED. |
| | NOTE: LABELS FOR DOORS AND WINDOWS U-FACTOR AND SHGC |
| | FACTORS SPECIFIED ON THE ENERGY CALCULATIONS WILL BE |
| | REQUIRED FOR INSPECTION WHEN ENERGY CALCULATIONS ARE |
| | NOT USING THE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 2- OWNER/AGENT TO SIGN AND DATE ENERGY CALCULATIONS FOR |
| | THE MAIN HOUSE ADDITION. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) RELOCATED FIXED FRENCH DOORS SHOWN ON DOOR SCHEDULE |
| | FOR MAIN HOUSE ADDITION (DOOR SCHEDULE NOT CHANGED). |
| | B) MODIFIED BITUMEN FOR GARAGE/HOME OFFICE TERRACE THAT |
| | IS DESIGNED TO RECEIVE STONE AS SPECIFIED ON PLANS. |
| | AND, CLEARLY IDENTIFY APPROVED ASSEMBLY AND PROVIDE |
| | SIGNED AND SEALED RAS 117 CALCULATIONS IF REQUIRED. |
| | INFORMATION SUBMITTED IS NOT A PRODUCT APPROVAL. |
| | |
| | 4- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS. |