2015-10-27 17:37:401ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090189
 10/29/15
  
 1) REFER TO SECTION R403.6.1 F BC-14 ENERGY
 CONSERVATION AND PROVIDE COOLING AND HEATING
 CALCULATIONS FOR THE NEW MITSUBISHI AC SYSTEM IN THE
 GARAGE. THE SUBMITTED CALCULATIONS ARE FOR THE 2ND
 FLOOR HOME OFFICE ONLY. THE NOTE ON THE PLAN " FOR
 DEHUMIDIFICATION PURPOSES ONLY" IS NOT APPLICABLE
 BECAUSE THE UNIT IS DESIGNED TO PROVIDE COOLING. FOR
 DEMHUMIDIFICATIONS PURPOSES ONLY, PLEASE PROVIDE A UNIT
 DESIGNED SPECIFICALLY FOR DEHUMIDIFCATION PURPOSES
 ONLY- A DEHUMIDIFIER. PLEASE NOTE IF CONDITIONING IS TO
 BE PROVIDED, THEN HEAT IS REQUIRED IN ACCORDANCE WITH
 SECTION R303.9 FBC-14 RESIDENTIAL.
 2) REFER TO SECTION R101.4.3 FBC-14 ENERGY CONSERVATION
 AND PROVIDE ENERGY CALCULATIONS FOR THE CONDITIONED
 GARAGE ADDITION. THE SUBMITTED CALCULATION IS FOR THE
 2ND FLOOR HOME OFFICE ONLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER