| Plan Review Notes For Permit 15090189 |
| Permit Number |
15090189 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-27 17:37:40 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15090189 | | | 10/29/15 | | | | | | 1) REFER TO SECTION R403.6.1 F BC-14 ENERGY | | | CONSERVATION AND PROVIDE COOLING AND HEATING | | | CALCULATIONS FOR THE NEW MITSUBISHI AC SYSTEM IN THE | | | GARAGE. THE SUBMITTED CALCULATIONS ARE FOR THE 2ND | | | FLOOR HOME OFFICE ONLY. THE NOTE ON THE PLAN " FOR | | | DEHUMIDIFICATION PURPOSES ONLY" IS NOT APPLICABLE | | | BECAUSE THE UNIT IS DESIGNED TO PROVIDE COOLING. FOR | | | DEMHUMIDIFICATIONS PURPOSES ONLY, PLEASE PROVIDE A UNIT | | | DESIGNED SPECIFICALLY FOR DEHUMIDIFCATION PURPOSES | | | ONLY- A DEHUMIDIFIER. PLEASE NOTE IF CONDITIONING IS TO | | | BE PROVIDED, THEN HEAT IS REQUIRED IN ACCORDANCE WITH | | | SECTION R303.9 FBC-14 RESIDENTIAL. | | | 2) REFER TO SECTION R101.4.3 FBC-14 ENERGY CONSERVATION | | | AND PROVIDE ENERGY CALCULATIONS FOR THE CONDITIONED | | | GARAGE ADDITION. THE SUBMITTED CALCULATION IS FOR THE | | | 2ND FLOOR HOME OFFICE ONLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|