| Plan Review Notes For Permit 15090174 |
| Permit Number |
15090174 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-24 05:37:54 | 1)SUBMIT UPDATED CERTIFICATIONS FOR THE FOR THE | | | COLLECTOR. THERE IS AN UPDATED CERTIFICATE LISTED ON | | | THE FSEC WEBSITE. | | | 2) THE PUMP AND WATER STORAGE TANK COMPANIES ARE NOT | | | LISTED ON THE FSEC WEBSITE. I COULD NOT FIND ANY INFO | | | ON THE FSEC WEBSITE FOR THESE PRODUCTS. CLARIFY. | | | 3)THERE ARE COLLECTOR MOUNTING DETAILS FROM A COMPANY | | | CALLED MORNING STAR SOLAR COLLECTORS. THIS IS NOT THE | | | COMPLANY WHOSE NAME IS ON THE FSEC CERTIFICATION. | | | CLARIFY. | | | 4) THE COLLECTOR MOUNTING DETAILS FROM MORNINGSTAR ARE | | | BARELY LEGIBLE AND THERE ARE ALSO MOUNTING DETAILS THAT | | | ARE ON THE SIGNED AND SEALED SHEET FROM ALLEN GEZELMAN. | | | CLARIFY. | | | 5) THE PLANS ARE DIFFICULT TO READ. THE PLANS SHALL BE | | | DRAWN AT A MINIMUM OF AN 1/8 INCH SCALE PER THE WPB | | | AMEND. TO FBC SEC. 107.2.1.4. | | | 6) THE PIPING DIAGRAM FOR THE COLLECTOR AND WATER | | | HEATER HAS NO PIPE SIZES ON ANY OF THE PIPE FOR THIS | | | SYSTEM. SHOW THE PIPE SIZES ON BOTH SETS. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|