| 2015-12-30 13:48:51 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC. |
| | THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE |
| | 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT |
| | DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC |
| | FIFTH EDITION. |
| | |
| | 2) THE PLANS REFERENCE THE 2008 NEC AND THE 2011 NEC IS |
| | THE EDITION THAT APPLIES TO THIS PROJECT. |
| | |
| | 3) THE OCCUPANCY TYPE FOR ONE AND TWO FAMILY DWELLINGS |
| | IS R-3 PER FBC SECTION 310. |
| | |
| | 4) SUBMIT TWO COPIES OF A SURVEY. FBC 107.2.1 |
| | |
| | 5) SHOW COMPLIANCE WITH FBC-R807.1 FOR ATTIC ACCESS. |
| | |
| | 6) DOUBLE UNDERLAYMENT IS REQUIRED FOR ASPHALT SHINGLE |
| | ROOFS WITH SLOPES LESS THAN 4/12 PER FBC-R905.2.3 |
| | |
| | 7) THE ROOF ZONE PRESSURE DIAGRAM ON S-3 AND STRUCTURAL |
| | NOTES ON S-2 HAVE -65 PSF FOR ROOF ZONES 2 AND 3. THE |
| | CORNER (ZONE 3) UPLIFT PRESSURES SHOULD BE MORE. ONE |
| | END OF THE ROOF IS A NOT A HIP. |
| | |
| | 8) THE STRUCTURAL NOTES ON S-2 HAVE THE COMPONENT AND |
| | CLADDING PRESSURES FOR WALL ZONE 5 AS -50 PSF. THIS IS |
| | A LITTLE LOW, IT SHOULD BE -54.1 PSF. FBC-R |
| | |
| | 9) FBC-R617.2.1 REQUIRES BUCKS TO EXTEND BEYOND THE |
| | INTERIOR FACE OF THE WINDOW OR DOOR FRAME. THE DRYWALL |
| | CAN NOT SUPPORT THE FRAME AS SHOWN IN THE DETAILS ON |
| | S-3. |
| | |
| | 10) NOT ALL PRODUCT APPROVALS FOR SECTIONAL GARAGE |
| | DOORS SPECIFY THE BUCKS TO WALL ATTACHMENT. SPECIFY THE |
| | REQUIRED BUCK ATTACHMENT TO BE USED WHEN ONE IS NOT |
| | PROVIDED IN THE PRODUCT APPROVAL. FBC 107.2.1 |
| | |
| | 11) SHOW COMPLIANCE WITH FBC-R311.7.8 FOR THE HANDRAILS |
| | AT THE STAIRS. |
| | |
| | 12) SHOW COMPLIANCE WITH FBC-R312.1 FOR THE GUARDS AT |
| | THE STAIRS. |
| | |
| | 13) PROVIDE COMPLETE STRUCTURAL DETAILS FOR THE STAIRS. |
| | SPECIFY ALL CONNECTIONS, ANCHORS AND CONNECTORS. FBC |
| | 107.2.1 |
| | |
| | 14) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| | THE DIFFERENT ROOFING MATERIALS, RIDGE VENT, |
| | WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR |
| | DOOR TYPES. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |