| 2016-04-11 14:11:59 | 2ND REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. WASHING MACHINE AND OUTDOOR SHOWER SHALL BE VENTED |
| | INDIVIDUALLY SHALL COMPLY WITH FBC RES. SEC. P3106.1 |
| | INDIVIDUAL VENT PERMITTED. |
| | EACH TRAP AND TRAPPED FIXTURE SHALL BE PERMITTED TO BE |
| | PROVIDED WITH AN INDIVIDUAL VENT. THE INDIVIDUAL VENT |
| | SHALL CONNECT TO THE FIXTURE DRAIN OF THE TRAP OR |
| | TRAPPED FIXTURE BEING VENTED. |
| | |
| | 2. SECOND FLOOR THE KITCHEN SHALL CONNECT DOWNSTREAM OF |
| | THE BATHROOM GROUP. SHALL COMPLY WITH FBC RES. SEC. |
| | P3108.1 HORIZONTAL WET VENT PERMITTED. |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO |
| | BE VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL |
| | BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL |
| | EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE |
| | DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST |
| | DOWNSTREAM FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN |
| | SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH |
| | BEING WET VENTED OR SHALL HAVE A DRY VENT. EACH |
| | WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO |
| | THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. |
| | |
| | 3. THE OUT DOOR SHOWER SHALL BE COVERED TO PREVENT |
| | STORM WATER FROM DRAINING INTO SANITARY SYSTEM. PER |
| | CODE OF ORDINANCES CITY OF WEST PALM BEACH, FLORIDA |
| | SEC.9-126.(5) |
| | |