| Notes |
| Date |
Text |
| 2016-02-11 06:34:27 | 1) SUBMIT THE OCCUPANT LOAD FOR THIS SPACE SINCE THE | | | OCCUPANCY HAS BEEN IDENTIFIED. COMPLY WITH 2014 FBC | | | TABLE .1004.1.2. | | | 2) A MINIMUM OF TWO TOILET ROOMS ARE REQUIRED ( ONE | | | MALE, ONE FEMALE) PER TABLE 403.1 OF 2014 FPC.( THIS | | | COULD NOT BE DETERMINED PREVIOUSLY DUE TO THE INCORRECT | | | OCCUPANCY THAT WAS NOTED ON THE PLANS). IF THERE ARE | | | ADDITIONAL SANITARY FACILITIES WITHIN 500 FEET OF THIS | | | STRUCTURE, THEY MIGHT BE ABLE TO BE USED TO MEET THIS | | | REQUIREMENT. TWO COPIES OF A SITE PLAN SHOWING THE | | | LOCATION AND DISTANCE OF THE ADDITIONAL FACILITIES | | | SHALL BE SUBMITTED IN ORDER TO MAKE A DECISION ON THIS | | | REQUIREMENT. | | | 3) HOT/TEMPERED WATER IS REQUIRED TO THE LAVATORY. SHOW | | | THIS ON THE WATER PIPING RISER.2014 FPC SEC. 607.1. | | | 4) SHT. A-400 - DETAILS #1 & # 3 THE GRAB BARS SHALL BE | | | MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014 | | | FBC-ACCESS. SEC. 609.4. | | | 5) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014 | | | FBC-ACCESS. SEC.307.2. AN OPTIONAL SKIRT MAY BE | | | REQUIRED TO KEEP THE LEADING EDGE BELOW 27 INCHES. | | | 6) SUBMIT THE SQUARE FEET OF THE POOL WATER SURFACE | | | AREA. SKIMMERS MAY BE UTILIZED WHEN THE POOL WATER | | | SURFACE IS 1000 SQUARE FEET OR LESS PER 2014 FBC SEC. | | | 454.1.6.5.3.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|