| 2016-02-10 06:31:52 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15090106 |
| | ADD: 1301 SUMMIT BLVD./ RENOVATIONS TO WHITE ALLIGATOR |
| | EXHIBIT. |
| | CONT: GAST CONSTRUCTION |
| | TEL: ( 321)622-6900 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. FEB. 10/ 2016 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED |
| | |
| | 3) 2ND REQUEST. PLEASE NOTE THE SUBMITTED FLOOD ZONE |
| | CERTIFICATES ARE PHOTOCOPIED, NOT ORIGINAL SIGNED AND |
| | SEALED DOCUMENTS FROM THE SURVEYOR. NONE OF THE 300 |
| | SERIES DRAWINGS INDICATE AT WHAT ELEVATION THE PROPOSED |
| | FLOOR ELEVATION ARE TO BE SET, INCLUDING THE UPPER AND |
| | LOWER POND LEVELS. THE PONDS SET AT OR BELOW BFE WOULD |
| | NEED ENGINEERING OR A HYDROSTATIC RELIEF VALVE. |
| | |
| | PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION OF |
| | STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD |
| | ZONE. FLOOD ZONE CERTIFICATES FBC BUILDING 1612 AND |
| | CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| | ADDITIONAL 6 INCHES OF ELEVATION. FINISH FLOOR |
| | ELEVATION OF 12 FT. - |
| | 6 INCHES OR HIGHER. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31/2015 |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | THE PERMIT APPLICATION INDICATES THE PROPOSED VALUE OF |
| | THIS PROJECT IS $200,000.00 DOLLARS IN VALUE. PLEASE |
| | PROVIDE COST IN THE PAST FOR THIS STRUCTURE AND THE |
| | ESTIMATED VALUE OF THE STRUCTURE AS PRESENTLY |
| | CONFIGURED. THE W. P. B. MUNI CODE DEFINITIONS: |
| | SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF |
| | REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO |
| | A STRUCTURE, TAKING PLACE DURING THE LIFE OF A |
| | STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR |
| | EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE |
| | STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE |
| | THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START |
| | OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF |
| | DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE |
| | OCCURRING. FOR THE PURPOSES OF THIS DEFINITION, |
| | "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN |
| | THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR |
| | OTHER STRUCTURAL PART OF THE BUILDING COMMENCES, |
| | WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL |
| | DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL |
| | IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT |
| | OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH, |
| | SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO |
| | ENSURE SAFE LIVING CONDITIONS. |
| | |
| | SEC. 94-546. - PROVISIONS FOR FLOOD HAZARD REDUCTION. |
| | (2) NONRESIDENTIAL CONSTRUCTION. ALL NEW CONSTRUCTION |
| | OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL, |
| | INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL |
| | EITHER HAVE THE LOWEST FLOOR, INCLUDING BASEMENT, |
| | ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE BASE |
| | FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT UTILITY AND |
| | SANITARY FACILITIES, BE FLOOD-PROOFED SO THAT BELOW SIX |
| | INCHES ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS |
| | WATERTIGHT, WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE |
| | PASSAGE OF WATER AND WITH STRUCTURAL COMPONENTS HAVING |
| | THE CAPABILITY OF RESISTING HYDROSTATIC AND |
| | HYDRODYNAMIC LOADS AND EFFECTS OF BUOYANCY. A |
| | REGISTERED PROFESSIONAL ENGINEER OR ARCHITECT SHALL |
| | CERTIFY THAT THE STANDARDS OF THIS SUBSECTION ARE |
| | SATISFIED. SUCH CERTIFICATION SHALL BE PROVIDED TO THE |
| | CITY ENGINEER. |
| | |
| | NOTE IF THE EXISTING STRUCTURE IS BELOW THE BASE FLOOD |
| | ELEVATION OF 12 FT. 6 INCHES AND SUBSTANTIAL |
| | IMPROVEMENTS ARE OVER THE 50% OF THE ASSESSED VALUE OF |
| | THE STRUCTURE AND THE OPTION IS TO INSTALL FLOOD VENTS |
| | TO ALLOW THE WATERS TO FLOW THROUGH AND RECEDE WHEN THE |
| | FLOOD STAGE IS OVER. PLEASE NOTE ANY NEW WORK |
| | RESTROOMS, ELECTRICAL EQUIPMENT & A/C CONDENSERS WILL |
| | NEED TO BE SET ABOVE THE 12FT. 6 INCH ELEVATION AND |
| | FLOOD ELEVATIONS ARE REQUIRED. |
| | |
| | 4) 2ND REQUEST. THE WHOLE AREA EAST OF I-95 FROM |
| | SOUTHERN BLVD. SOUTH TO THE CITY GOLF COURSE IS IN A |
| | QUESTIONABLE SOILS ZONE, MUCK AND ORGANICS!!!! THE |
| | REMOVAL OF A NOTE ON THE STRUCTURAL PAGES DOES NOT |
| | REMOVE THE LOCATION FROM A QUESTIONABLE SOILS ZONE |
| | WHERE BEARING VALUES DEPENDS ON THE VALUES FROM THE |
| | SOILS TEST. THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN |
| | SUBMITTED. 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS |
| | REPORT IS ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING |
| | CAPACITY OF THE SOILS WILL BE. |
| | |
| | 5) COMPLIED. |
| | |
| | 6-7) THE DESIGNER OF RECORD HAS ELECTED TO SUBMIT THE |
| | PRODUCT APPROVAL AFTER PERMIT ISSUANCE. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS. |
| | PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. 2014 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (F) SKYLIGHT REPAIR OR REPLACEMENT? |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) NEW COMMENT: SHEET S3.0 INDICATES POOLS BY OTHERS, A |
| | SEPARATE PERMIT AND PLANS WILL BE REQUIRED. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |