| Plan Review Notes For Permit 15090101 |
| Permit Number |
15090101 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-10 12:27:19 | MECHANICAL PROVISIOS; | | | PERMIT #15090101 | | | 2/10/16 | | | | | | 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE UPONOR PEX CHILLER PIPING SHALL BE | | | REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR, AND | | | ALL SITE AT TIME OF INSPECTION. | | | 2) THE MIAMI-DADE NOA AND/OR FLORIDA PRODUCT APPROVAL | | | FOR THE LOUVERS SHALL BE REVIEWED AND APPROVED WITH | | | SIGNATURE BY THE EOR AND SUBMITTED TO THE BUILDING | | | DEPARTMENT PRIOR TO 1ST INSPECTION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | |
|