| Date |
Text |
| 2016-02-10 10:37:13 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15090101 |
| | ADD: 1301 SUMMIT BLVD. |
| | PANTHER RENOVATIONS/ SPOONBILL/IBIS/ OTTER HOLDING |
| | STRUCTURE |
| | CONT: GAST CONSTRUCTION |
| | TEL: (321)622-6900 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. SEPT. 27/ 2015 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | |
| | 4) 2ND REQUEST. PLEASE NOTE THE SUBMITTED FLOOD ZONE |
| | CERTIFICATES ARE PHOTOCOPIED, NOT ORIGINAL SIGNED AND |
| | SEALED DOCUMENTS FROM THE SURVEYOR. NONE OF THE 300 |
| | SERIES DRAWINGS INDICATE AT WHAT ELEVATION THE PROPOSED |
| | FLOOR ELEVATION ARE TO BE SET. |
| | PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION OF |
| | STRUCTURES; THE PROPERTY IS LOCATED IN AN A-7 FLOOD |
| | ZONE. FLOOD ZONE CERTIFICATES |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH |
| | FLOOR ELEVATION OF 12 FT. - |
| | 6 INCHES OR HIGHER. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31/2015 |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 5) 2ND REQUEST. THE WHOLE AREA EAST OF I-95 FROM |
| | SOUTHERN BLVD. SOUTH TO THE CITY GOLF COURSE IS IN A |
| | QUESTIONABLE SOILS ZONE, MUCK AND ORGANICS!!!! THE |
| | REMOVAL OF A NOTE ON THE STRUCTURAL PAGES DOES NOT |
| | REMOVE THE LOCATION FROM A QUESTIONABLE SOILS ZONE |
| | WHERE BEARING VALUES DEPENDS ON THE VALUES FROM THE |
| | SOILS TEST. THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN |
| | SUBMITTED. 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS |
| | REPORT IS ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING |
| | CAPACITY OF THE SOILS WILL BE. |
| | SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS INDICATES |
| | THERE IS TO HAVE A SOILS REPORT INVESTIGATION THIS SITE |
| | HAS QUESTIONABLE SOILS IN BEARING CAPACITY. THIS REVIEW |
| | CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. 2014 FBC-B |
| | 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS ALSO TO |
| | PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY OF THE |
| | SOILS WILL BE. |
| | |
| | 6) COMPLIED. WIND DESIGN CRITERIA / PRESSURES. |
| | |
| | 7A-7B) COMPLIED. THE DESIGNER OF RECORD HAS ELECTED TO |
| | SUBMIT THE PRODUCT APPROVAL AFTER PERMIT ISSUANCE. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107.3.4.2 DEFERRED SUBMITTALS. |
| | 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | |
| | 8) COMPLIED. SHEET A-001. OCCUPANCY TYPE: A3. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |