| Plan Review Notes For Permit 15090101 |
| Permit Number |
15090101 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-24 06:52:16 | 1) SHT. A-001 - THE PLANS REFER TO THE 2010 FBC. THE | | | CODE IN EFFECT IS THE 2014 FBC. REVISE NOTE. | | | 2) SUBMIT A COMPLETE PIPING RISER DIAGRAM FOR THE | | | IBIS/SPOONBILL WATER FEATURE. PIPING DIAGRAM SHALL | | | INCLUDE SSUPPLY AND RETURN LINES, MAIN DRAINS, PUMP, | | | PUMP CURVE, ETC. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SUBMIT MANUFACTURER SPEC SHEETS FOR THE MAIN DRAINS, | | | THE PUMP, PUMP CURVE, ETC.WPB AMEND.TO FBC SEC. | | | 107.2.1. | | | 4) SHT. IR-1 - SHOWS 4 - 2 INCH LINES BY THE OVERHEAD | | | PANTHER WALK BUT THEY ARE ALSO SHOWN AS 3/4 INCH LINES | | | ON THE PLAN. CLARIFY. | | | 5) SHT. IR-1 - THERE ARE A LOT OF IRRIGATION LINES ON | | | THE PLAN THAT HAVE NO PIPE SIZES. AT THE VERY LEAST, | | | SIZE THE MAN BRANCH LINES. | | | 6) SHT. IR-2 - THE DETAILS AND PRINTED TEXT ARE VERY | | | LIGHT AND ILLEGIBLE. SUBMIT A REVISED DRAWING THAT IS | | | CLEAR IN TEXT AND DETAILS.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 7) SUBMIT AN ENLARGED FLOOR PLAN FOR THE NEW RESTROOM. | | | THE RESTROOM SHALL BE FULLY ACCESSIBLE.2014 FBC - | | | ACCESSIBILITY SEC.202.1, 213.1, 213.2. | | | 8) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE | | | NEW RESTROOM. WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|