| 2015-10-01 12:32:26 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE |
| | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. GENERAL LIGHTING NOTES #6 QUOTED A SECTION OF THE |
| | FBC THAT HAS NO BEARING TO THIS JOB. |
| | 2. GENERAL LIGHTING NOTES #7 QUOTED AN INCORRECT CODE. |
| | THIS JOB IS GOVERNED BY THE 2011 EDITION OF THE NEC. |
| | 3. ALL LIGHTING SHALL COMPLY WITH 5TH EDITION |
| | FBC-ENERGY CONSERVATION 2014 SECTION C405. |
| | A) YOU SHALL PROVIDE A LIGHT DENSITY ALLOWANCE CHART |
| | SHOWING LIGHTING COMPLIANCE. |
| | B) YOU SHALL PROVIDE A LIGHTING DIAGRAM |
| | C) YOUR FEEDERS SHALL BE DESIGNED FOR A MAXIMUM 2% |
| | VOLTAGE DROP & BRANCH CIRCUITS FOR NO MORE THAN 3% VD. |
| | 4. EXIT LIGHTS AS REQUIRED BY FBC SECTION 1011 SHALL BE |
| | INDICATED ON DRAWINGS. |
| | 5. GENERAL ELECTRICAL NOTES #6 AGAIN QUOTED THE 2008 |
| | NEC AND NOT THE 2011. |
| | 6. YOU SHALL PROVIDE LOAD CALCS IN ACCORDANCE WITH NEC |
| | 220.16. |
| | 7. YOU SHALL SUBMIT A SITE SPECIFIC ELECTRICAL RISER |
| | DIAGRAM INDICATING THE CONDUCTOR SIZING FOR VOLTAGE |
| | DROP ALLOWANCES AND THE LOCATION OF ALL PANELS |
| | ASSOCIATED WITH THE SITE. |
| | 8. A CIRCUIT DIRECTORY AS REQUIRED BY NEC 408.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |