| Plan Review Notes For Permit 15090051 |
| Permit Number |
15090051 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-20 14:41:59 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | UPDATE THE PLAN TO INDICATE COMPLIANCE WITH THE | | | FOLLOWING: | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE IMPACT RESISTANT SKYLIGHT | | | SUBMITTAL. | | | | | | FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED IN | | | BEDROOM 2 AS FOLLOWS: WHERE EMERGENCY ESCAPE AND RESCUE | | | OPENINGS ARE PROVIDED THEY SHALL HAVE A SILL HEIGHT OF | | | NOT MORE THAN 44 INCHES (1118 MM) MEASURED FROM THE | | | FINISHED FLOOR TO THE BOTTOM OF THE CLEAR OPENING. | | | R310.1.1 MINIMUM OPENING AREA GRADE FLOOR OPENINGS | | | SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5 SQUARE FEET | | | R310.1.2 MINIMUM OPENING HEIGHT. | | | THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES | | | R310.1.3 MINIMUM OPENING WIDTH. | | | THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES | | | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | |
|