| 2015-12-14 17:06:46 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 5TH EDITION RESIDENTIAL |
| | |
| | 1. FROM PREVIOUS LIST, PLANS ARE TO INCLUDE THE WIND |
| | DESIGN CRITERIA, FBC 5TH ED. RESIDENTIAL 301 (WIND |
| | SPEED, EXPOSURE CLASSIFICATION, RISK CATEGORY) AS WELL |
| | AS THE METHOD USED FOR DESIGN (ONE OF THE METHODS IN |
| | SECTION 301). IF ENGINEERING (ASCE7-10) IS USED AS THE |
| | METHOD OF DESIGN, PROVIDE CALCULATIONS. |
| | |
| | NOT ADDRESSED. REVIEW WILL BE DONE AFTER THE |
| | INFORMATION HAS BEEN PROVIDED. AN ACCURATE REVIEW IS |
| | NOT POSSIBLE WITHOUT THIS INFORMATION. |
| | |
| | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | COMPONENTS AND CLADDING. AS FLINTLASTIC SPEC SHEETS |
| | WERE SUBMITTED, IT APPEARS THAT A ROOF IS PROPOSED. |
| | PROVIDE THE PRODUCT APPROVAL FOR THE ROOF COVERING, AND |
| | ON THE PRODUCT APPROVAL, INDICATE WHICH OPTION IS |
| | PROPOSED. IF THE PRODUCT APPROVAL DOES NOT REQUIRE |
| | ENGINEERING FOR ENHANCED FASTENING, IT IS POSSIBLE THAT |
| | THIS MAY BE DONE FOR YOU (BUT YOU NEED TO PROVIDE THE |
| | ROOF COVERING PRODUCT APPROVAL). |
| | |
| | NOT ADDRESSED. PRODUCT APPROVAL ALSO REQUIRED FOR |
| | STRUCTURAL COMPONENTS. |
| | |
| | 3. PLANS ARE INCOMPLETE. FOR INSTANCE, SHEET 2 |
| | SPECIFIES "STEEL U BRACKET." IS THIS BEING |
| | MANUFACTURERED OR IS AN ENGINEERED COMPONENT PROPOSED? |
| | |
| | SHEET 5 SPECIFIES "SIMPSON STRONG TIE OR EQUAL." |
| | INFORMATION IS TOO GENERAL AS THIS COMPANY |
| | MANUFACTURERS THOUSANDS OF CONNECTORS. ALL STRUCTURAL |
| | INFORMATION IS TO BE COMPLETE. AFTER WIND DESIGN |
| | CRITERIA AND METHOD OF DESIGN HAVE BEEN ESTABLISHED, |
| | THE SPECIFIC INFORMATION WILL BE REVIEWED. CALCUATIONS |
| | MAY BE REQUIRED. |
| | |
| | |