| 2015-09-02 07:02:29 | 1) THE GAS SHALL BE SUBMITTED AS A SEPARATE PERMIT. |
| | SUBMIT A SEPARATE GAS APPLICATION AND TWO SETS OF PLANS |
| | FOR REVIEW. THE GAS RISER SHALL SHOW ALL PIPE SIZES, |
| | PSI OF THE SYSTEM, DEVELOPED LENGTH TO FURTHEST OUTLET, |
| | TOTAL BTU LOAD ON THE SYSTEM, TYPE OF PIPE, TYPE OF GAS |
| | APPLIANCES, ETC. SUBMIT TWO COPIES OF MANUFACTURER'S |
| | SPECIFICATIONS THAT SHOW THAT THE TANKLESS WATER HEATER |
| | IS LISTED AND LABELED AS REQUIRED BY 2014 |
| | FBC-RESIDENTIAL SEC. G2404.3. THE SPECS THAT WERE |
| | SUBMITTED WITH THIS PERMIT DO NOT SHOW THAT THE UNIT IS |
| | LISTED AND LABELED. WPB AMEND. TO FBC SEC. 107.3.5.3. |
| | 2) CLARIFY NOTE #1 "SEWER TO RUN TO NEXT DWELLING AT |
| | LATER DATE." THE SEWER CANNOT RUN ACROSS ADJACENT |
| | PROPERTY LINES WITHOUT A RECORDED UTILITY EASEMENT. |
| | 3) SUBMIT A SANITARY RISER TO SHOW HOW THE SANITARY |
| | LINES WILL BE INSTALLED. THE FLAT DRAWING IS CONFUSING |
| | AND UNCLEAR. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) CLEARLY INDICATE HOW THE SANITARY LINES WILL BE RUN |
| | TO THE BATHROOM. WILL ANY TUNNELING UNDER THE HOUSE |
| | SLAB BE REQUIRED? IF SO, THE FOLLOWING SHALL BE |
| | REQUIRED: |
| | PLUMBING REPAIR TUNNEL WORK |
| | A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE |
| | SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO |
| | EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED, |
| | THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO |
| | EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS. |
| | DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED |
| | THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE |
| | CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND |
| | BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED BELOW |
| | GROUND PER THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| | SECTION 318 AND THE FLORIDA BUILDING CODE, BUILDING, |
| | SECTION 2603.8. |
| | 5) A CLEANOUT IS REQUIRED AT THE SEWER CONNECTION TO |
| | THE CITY LATERAL. |
| | 6) SHOW THE LOCATION OF THE WATER METER ON THE PLAN. |
| | |
| | PLUMBING PLAN REVIEW |