| Plan Review Notes For Permit 15081167 |
| Permit Number |
15081167 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-02 18:52:26 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHOW COMPLIANCE WITH FBCR 4501.17 FOR REQUIRED | | | SWIMMING POOL BARRIER. SPECIFY THE METHOD OR | | | COMBINATION OF METHODS THAT WILL BE USED. | | | | | | 2) SECTION R403.9.2 OF THE 2014 ENERGY CONSERVATION | | | CODE REQUIRES TIME SWITCHES FOR PUMPS AND HEATERS. | | | | | | 3) SECTION R403.9.3 OF THE 2014 ENERGY CONSERVATION | | | CODE REQUIRES HEATED POOLS TO HAVE COVERS TO REDUCE | | | HEAT LOSS. |
|