| Date |
Text |
| 2015-09-10 10:34:57 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THERE WAS NO CROSS SECTION OF THE LONG DIMENSION |
| | POOL. SPECIFY THE DEPTH BOTH ENDS OF THE POOL. FBC |
| | 107.2.1 |
| | |
| | 2) THE POOL IS REQUIRED TO COMPLY WITH R4501.18 LADDERS |
| | AND STEPS. |
| | ALL POOLS WHETHER PUBLIC OR PRIVATE SHALL BE PROVIDED |
| | WITH A LADDER OR STEPS IN THE SHALLOW END WHERE WATER |
| | DEPTH EXCEEDS 24 INCHES (610 MM). IN PRIVATE POOLS |
| | WHERE WATER DEPTH EXCEEDS 5 FEET (1524 MM), THERE SHALL |
| | BE LADDERS, STAIRS OR UNDERWATER BENCHES/SWIMOUTS IN |
| | THE DEEP END. WHERE MANUFACTURED DIVING EQUIPMENT IS TO |
| | BE USED, BENCHES OR SWIMOUTS SHALL BE RECESSED OR |
| | LOCATED IN A CORNER. |
| | EXCEPTION: IN PRIVATE POOLS HAVING MORE THAN ONE |
| | SHALLOW END, ONLY ONE SET OF STEPS ARE REQUIRED. A |
| | BENCH, SWIM-OUT OR LADDER MAY BE USED AT ALL ADDITIONAL |
| | SHALLOW ENDS IN LIEU OF AN ADDITIONAL SET OF STEPS. |
| | |
| | 3) THE FLORIDA BUILDING CODE 5TH EDITION (2014) |
| | RESIDENTIAL HAS THE SWIMMING POOL ELECTRICAL PROVISIONS |
| | IN CHAPTER 42 AND THE PRIVATE SWIMMING POOL PROVISIONS |
| | ARE NOW IN CHAPTER 45. THE CODE SECTIONS REFERENCED ON |
| | THE PLAN ARE INCORRECT. |
| | |
| | 4) THE VALUE SPECIFIED FOR THE POOL OF $20,000.00 |
| | APPEARS TO BE LOW. SUBMIT A COPY OF THE SIGNED CONTRACT |
| | TO VERIFY THE VALUATION. FBC 109.3 |