| 2016-01-08 08:58:22 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | | | | | APPROVED WITH EXCEPTION. PROVIDE A REVISION TO | | | DEMONSTRATE COMPLIANCE WITH THE SECTION BELOW AS THE | | | NEW EXIT STAIR IR REQUIRED TO BE ILLUMINATED. | | | | | | FBCRE3903.3 ADDITIONAL LOCATIONS. | | | AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET | | | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED | | | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT | | | LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL | | | BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR | | | SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL | | | ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED | | | GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A | | | VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN | | | OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS | | | ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A | | | WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT | | | INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS | | | WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE | | | RISERS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|