| 2015-09-03 14:33:34 | 1) THE PLANS SHOW A NEW TANKLESS WATER HEATER TO BE |
| | INSTALLED. GAS SHALL BE INSTALLED UNDER A SEPARATE |
| | PERMIT AND 2 COPIES OF A GAS RISER DIAGRAM SHALL BE |
| | SUBMITTED ALONG WITH TWO COPIES OF MANUFACTURER'S |
| | SPECIFICATIONS SHOWING THAT THE DEVICE IS LISTED AND |
| | LABELED IN ACCORDANCE WITH THE 2014 FBC-RESIDENTIAL |
| | SEC. G2404.3. |
| | 2) SUBMIT A WATER PIPING RISER DIAGRAM FOR THE TANKLESS |
| | WATER HEATER SHOWING THE COLD WATER LINE SIZE AND |
| | CONNECTION TO THE EXISTING SYSTEM AND THE HOT WATER |
| | PIPING CONNECTION TO THE EXISTING SYSTEM. WPB AMEND. TO |
| | FBC SEC. 107.3.5.3. |
| | 3) THE PLANS ARE SEVERELY DEFICIENT IN INFORMATION FOR |
| | A GAS REVIEW. COMPLY WITH ALL THE FOLLOWING COMMENTS: |
| | 4). SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC-2014 FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. |
| | |
| | 5) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 6) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). |
| | |
| | 7) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE |
| | SEC. 402.4.1. |
| | |
| | 8) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2, AND |
| | 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED PER |
| | SEC.301.3. THE SUBMITTED DOCUMENTS DO NOT SHOW |
| | COMPLIANCE. |
| | |
| | 9) CLARIFY COMMENT #1 "PVC WILL CONTINUE TO NEXT |
| | DWELLING AT A LATER DATE." THE UNDERGROUND SANITARY |
| | /WATER SERVICE LATERALS CANNOT CROSS THROUGH THE |
| | ADJACENT PROPERTY WITHOUT A RECORDED UTILITY EASEMENT. |
| | UTILITY EASEMENTS, EASEMENT LOCATION AND ASSOCIATED |
| | RESTRICTIVE PROPERTY COVENANTS ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL FOR REVIEW AND APPROVAL PRIOR TO |
| | RECORDING. SAID DOCUMENTS SHALL BE RECORDED AND PROOF |
| | OF RECORDING ON THE PLAT, AND ACCEPTANCE BY THE CITY |
| | SURVEYOR, SHALL BE PROVIDED. |
| | 10) SUBMIT A SANITARY AND WATER RISER DIAGRAM.THE PLAN |
| | DRAWING SUBMITTED IS CONFUSING AND UNCLEAR. WPB AMEND. |
| | TO FBC SEC. 107.3.5.3. |
| | 11) THE DRAWING SHOWS THE WATER AND SANITARY BEING |
| | REPLACED IN A BATHROOM. HOW IS THIS PIPE BEING |
| | INSTALLED? WILL THERE BE ANY TUNNELING UNDER THE |
| | EXISTING SLAB? IF SO, A CLEAR AND LEGIBLE SANITARY |
| | RISER DIAGRAM SHALL BE SUBMITTED SHOWING ALL PIPE |
| | SIZES, CONNECTION POINTS TO EXISTING PIPING, HOW THE |
| | NEW PIPE WILL BE SUPPORTED, THE TYPE OF ADAPTERS USED |
| | FOR THE CONNECTIONS TO EXISTING PIPE, AND THE LOCATIONS |
| | OF REQUIRED CLEANOUTS. DETAILS AND BACKFILLING |
| | PROCEDURES SHALL BE SUBMITTED THAT CLEARLY SHOW HOW THE |
| | STRUCTURAL INTEGRITY OF THE CONCRETE SLAB WILL BE |
| | MAINTAINED DURING EXCAVATION AND BACKFILLING. |
| | STRUCTURAL FOAM IS NOT PERMITTED BELOW GROUND PER THE |
| | FLORIDA BUILDING CODE, RESIDENTIAL, SECTION 318 AND THE |
| | FLORIDA BUILDING CODE, BUILDING, SECTION 2603.8. |
| | 12) A CLEANOUT IS REQD. AT THE SEWER CONNECTION TO THE |
| | CITY LATERAL. |
| | 13) THE PLUMBING WORK AND GAS SHALL BE TWO SEPARATE |
| | PERMIT APPLICATIONS.SUBMIT SEPARATE PERMIT APPLICATIONS |
| | AND PLANS FOR THE PLUMBING WORK AND THE GAS WORK. THERE |
| | IS ALSO ANOTHER PERMIT APPLICATION FOR SOME WORK BEING |
| | DONE AT THIS LOCATION THAT SHOWS A NEW TANKLESS WATER |
| | HEATER BUT HAS NO GAS NOR PLUMBING PIPING SHOWN ON IT. |
| | CLARIFY. |
| | |
| | PLEASE CONTACT ME AS THIS SUBMITTAL IS EXTREMELY |
| | CONFUSING. |
| | |