| 2015-12-29 17:13:58 | RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 1- NEW CLAY TILE FLORIDA PRODUCT APPROVAL FL17152-R1 |
| | WAS SUBMITTED. LIMITATION #3 ON THIS PRODUCT APPROVAL |
| | SPECIFIES THAT TILES SHALL BE MECHANICALLY ATTACHED FOR |
| | WIND LOAD RESISTANCE. PRODUCT APPROVAL SUBMITTED |
| | DOESN'T SPECIFY THE TILE ATTACHMENT RESISTANCE. NEED |
| | THIS INFORMATION TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). PROVIDE COMPLETE CALCULATIONS SHOWING HOW THE |
| | PROPOSED MECHANICAL ATTACHMENT IS GOING TO MEET THE |
| | DESIGN PRESSURES OF SEC. R301. |
| | NOTE: NOA 14-0107.02 PREVIOUSLY SUBMITTED HAD ALL THIS |
| | INFORMATION. THE ONLY THING THAT WAS MISSING WAS THE |
| | PRODUCT APPROVAL FOR THE ADHESIVE TO BE USED. |
| | |
| | 2- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R15 |
| | SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301. THIS BUILDING IS LOCATED |
| | IN EXPOSURE "C". IF THE SELECTED ASSEMBLY DOESN'T MEET |
| | THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED |
| | AND SEALED RAS 117 CALCULATIONS WOULD BE REQUIRED. SEE |
| | NOTE #8 ON PAGE 2 OF 76. |
| | (REPEAT COMMENT. NOT ADDRESSED AT ALL. THIRD TIME). |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |