| 2015-10-16 18:14:10 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 1- ORIGINALLY THIS HOUSE WAS DESIGNED TO HAVE SHINGLES |
| | ROOFING. PROPOSAL TO INSTALL CLAY TILES REQUIRES |
| | ENGINEERING ANALYSIS TO VERIFY IF THE STRUCTURE IS |
| | ADEQUATE TO RECEIVE THE ADDITIONAL LOAD. SEC. 107.2.1.3 |
| | CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | ENGINEER LETTER SUBMITTED: |
| | (1) IT APPEARS THAT WRONG HOUSE WAS INSPECTED BY THE |
| | ENGINEER. IT LOOKS LIKE THE ENGINEER INSPECTED THE |
| | HOUSE LOCATED AT 505 38TH STREET AS STATED ON THE |
| | LETTER. THE HOUSE FOR THIS PERMIT IS 502 38TH STREET, |
| | WHICH IS LOCATED ACROSS THE STREET. THE BUILDING |
| | FRAMING SYSTEM IS DIFFERENT FOR BOTH HOUSES. ONE HOUSE |
| | WAS BUILT IN 1954 AND THE OTHER ONE WAS BUILT IN 1925. |
| | THERE MAY NOT BE A TRUSS SYSTEM ON THE HOUSE BUILT IN |
| | THE 1925'S. ENGINEER TO REVISE ADDRESS AND PROVIDE |
| | COMPLETE ROOF FRAMING AND SUPPORTING WALLS INFORMATION |
| | FOR THE CORRECT HOUSE. SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | (2) THE ORIGINAL ROOF COVERING OF THIS HOUSE WAS |
| | SHINGLES NOT CLAY TILES. REVISE AS REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | (3) ENGINEER TO PROVIDE ALL HIS INFORMATION AND THE |
| | FIRM CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY |
| | SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR THE TILE ADHESIVE LISTED ON THE |
| | CLAY TILE NOA. |
| | (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | 3- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R15 |
| | SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301. THIS BUILDING IS LOCATED |
| | IN EXPOSURE "C". IF THE SELECTED ASSEMBLY DOESN'T MEET |
| | THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED |
| | AND SEALED RAS 117 CALCULATIONS WOULD BE REQUIRED. SEE |
| | NOTE #8 ON PAGE 2 OF 76. |
| | (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |