| 2015-09-09 07:31:57 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15081111 |
| | ADD: 444 BUNKER RANCH RD. |
| | CONT: CURY BUILDING & DESIGN |
| | TEL: (561)718-1398 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. SEPT. 09/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S07 CODE REFERENCE SHEET. LIST THE 2014, 5TH |
| | EDITION OF THE FLORIDA BUILDING CODE. THE PLANS ARE |
| | SILENT TO WHAT DESIGN THE PLANS WERE DESIGN TO UNDER |
| | THE 2014 FBC-EXISTING BUILDING CODE, 301.1. |
| | |
| | 2) SHEET S07 STUCTURAL NOTES UNDER THE HEADING OF |
| | MATERIALS THE STRENGTH OF CONCRETE IS DECLARED FOR |
| | SLABS, COLUMNS AND BEAMS, SHEET S02 THE COLUMN SCHEDULE |
| | UNIT C6 IS FILLED CELL MASONRY THE PLANS INDICATE THE |
| | USE OF 3000 PSI CONCRETE, IN FILED CELL MASONRY |
| | SHOULDN'T THE USE OF GROUT BE USED INSTEAD OF CONCRETE. |
| | ACI 530 1.16.1. & TABLE 1.16.1 GROUTING MINIMUM SPACES. |
| | |
| | 3) SHEET S2 FOOTING SCHEDULE FOOTING F2-F6 INDICATES |
| | THE WIDTH & LENGTH OF THE FOOTING BUT NOT THE HEIGTH. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) SHEET S2 FOOTING SCHEDULE F4 DOES NOT PROVIDE AT |
| | WHAT CENTER TO CENTER IN INCHES WHAT THE STEEL MATS ARE |
| | TO BE INSTALLED. 107.2.1.3 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |