2015-12-17 10:42:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. S1.4.5A, ENGINEER'S LETTER STATES THAT FLOOR LIVE
 LOAD FOR 2ND FLOOR AMENITY AREA IS 50 LB, BUT FBC TABLE
 1607 REQUIRES 100 LB FOR ASSEMBLY USES.
  
 PLEASE INCORPORATE THE LIVE LOAD INTO THE PLAN, FBC
 107. REVISE OCCUPANCY CLASSIFICATION FOR THE AREA TO A
 USE WITH FALLS WITHIN THE 50 LB. LIMITATION FOR THIS
 AREA (A SHEETS).
  
 PLEASE ADVISE WHEN THIS REVISION IS RESUBMITTED. THE
 BUILDING PLAN REVIEW WILL BE EXPEDITED.
  
  
  