| Plan Review Notes For Permit 15081110 |
| Permit Number |
15081110 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-04 10:38:33 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15081110 | | | MASTER #14030096 | | | | | | 1) THE RESPONSE NARRATIVE TO COMMENT #2 FROM THE 1ST | | | REVIEW INDICATES THAT THE SECOND FLOOR ATRIUM WALL THAT | | | THE DUCT IS PENETRATED IS NOT A FIRE-RATED WALL, AND | | | THEREFORE NO DAMPER IS REQUIRED. PLEASE REFER TO | | | SECTION 404.6 FBC-10 AND INDICATE WHICH OF THE THREE | | | EXCEPTIONS LISTED IS BEING USED TO DE-RATE THE WALL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] |
|