| 2015-11-19 15:10:12 | WE CANNOT BASE OUR INSPECTIONS/PLAN REVIEWS ON FUTURE |
| | DESIGNS AND RISK THE CONSTRUCTION BEING LEFT UNFINISHED |
| | AND NON-CODE COMPLIANT. A FLOOR-TO-FLOOR FIRE |
| | SEPARATION IS REQUIRED BY CODE OR THE DESIGN NEEDS TO |
| | WHOLLY COMPLY AS EITHER A COMMUNICATING SPACE, AN |
| | ATRIUM, A MEZZANINE OR A CONVENIENCE OPENING. THE |
| | CURRENT FIELD CONDITIONS DO NOT FULLY COMPLY WITH ANY |
| | OF THESE OPTION. HENCE, A FINAL FIRE INSPECTION WILL |
| | NOT PASS INSPECTION AND A CERTIFICATE OF OCCUPANCY WILL |
| | NOT BE ISSUED UNTIL THE 2ND FLOOR AMENITIES AREA DESIGN |
| | AND CONSTRUCTION HAS BEEN COMPLETED. THIS ISSUE |
| | GENERATED THE FOLLOWING COMMENTS DURING FIRE PLAN |
| | REVIEW OVER A YEAR AGO (09/30/14): |
| | |
| | 705 NORTH OLIVE AVENUE |
| | PERMIT #14030096 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****PROVISO - THE AMENITIES/LEASING OFFICE IS NOT |
| | APPROVED FOR CONSTRUCTION AT THIS TIME UNTIL THE |
| | FLOOR/CEILING OPENINGS DESIGN HAS BEEN RESOLVED***** |
| | |
| | ROUND #3 COMMENTS: |
| | REPEAT COMMENT - SHEET A-0.1.2: SEVERAL AREAS IN THE |
| | AMENITIES/LEASING OFFICE ARE OPEN TO THE FLOOR BELOW. |
| | THE DESIGN SHALL CONFORM TO SECTION 8.6 VERTICAL |
| | OPENINGS AS EITHER A COMMUNICATING SPACE, CONVENIENCE |
| | OPENING, ATRIUM, OR MEZZANINE. FOR INSTANCE, EACH |
| | OCCUPANT NOT IN THE COMMUNICATING SPACE (SUCH AS |
| | AMENITY SECOND FLOOR REST ROOM) NEEDS TO HAVE ACCESS TO |
| | AT LEAST ONE EXIT WITHOUT HAVING TO ENTER THE |
| | COMMUNICATING SPACE, OR AS A CONVENIENCE OPENING, THE |
| | OPENINGS NEED TO BE SEPARATED FROM CORRIDORS. |
| | |
| | WESLEY R. JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR/INSPECTOR |
| | BUREAU OF FIRE PREVENTION |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE STATION #1: 561.804.4752 |
| | CONST. SERVICES : 561.805.6730 |
| | [email protected] |
| | |
| | |
| | THE SECOND FLOOR AMENITIES AREA IS NO LONGER FIRE |
| | SEPARATED FROM THE FIRST FLOOR AS IS REQUIRED FOR |
| | FLOOR-TO-FLOOR SEPARATION. OTHERWISE, AS PREVIOUSLY |
| | INDICATED IN 2014: SHEET A-0.1.2: SEVERAL AREAS IN THE |
| | AMENITIES/LEASING OFFICE ARE OPEN TO THE FLOOR BELOW. |
| | THE DESIGN SHALL CONFORM TO SECTION 8.6 VERTICAL |
| | OPENINGS AS EITHER A COMMUNICATING SPACE, CONVENIENCE |
| | OPENING, ATRIUM, OR MEZZANINE. FOR INSTANCE, EACH |
| | OCCUPANT NOT IN THE COMMUNICATING SPACE (SUCH AS |
| | AMENITY SECOND FLOOR REST ROOM) NEEDS TO HAVE ACCESS TO |
| | AT LEAST ONE EXIT WITHOUT HAVING TO ENTER THE |
| | COMMUNICATING SPACE, OR AS A CONVENIENCE OPENING, THE |
| | OPENINGS NEED TO BE SEPARATED FROM CORRIDORS. |