| Plan Review Notes For Permit 15081110 |
| Permit Number |
15081110 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-10 12:56:55 | 1ST REVIEW: FBC 2010 MECHANICAL | | | REVISION #15081110 | | | MASTER #14030096 | | | 9/10/15 | | | | | | 1) PROVIDE THE REVISED M-2.1.2 PLAN SHEET- THE REVISION | | | #10 NARRATIVE INDICATES THE PLAN WAS REVISED TO SHOW | | | NEW VENTILATION FANS. PLEASE BE SURE TO PROVIDE | | | VENTILATION CALCULATIONS, EQUIPMENT SCHEDULES, OPENING | | | PROTECTIONS (IF APPLICABLE), INSTALLATION DETAILS, AND | | | REVISED ELECTRICAL PLANS | | | 2) SHEET M-4.4: PLEASE CLARIFY WHY THE FIRE DAMPER WAS | | | REMOVED FROM THE DUCT PENETRATING THE 2ND FLOOR WALL | | | ABOVE THE FITNESS CENTER- THE WALL, AS SHOWN IN THE | | | LIFE SAFETY PLAN A-0.1.2, IS A FIRE-RATED WALL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|