| 2015-09-18 13:37:11 | THE SECOND FLOOR AMENITIES AREA IS NO LONGER FIRE | | | SEPARATED FROM THE FIRST FLOOR AS IS REQUIRED FOR | | | FLOOR-TO-FLOOR SEPARATION. OTHERWISE, AS PREVIOUSLY | | | INDICATED IN 2014: SHEET A-0.1.2: SEVERAL AREAS IN THE | | | AMENITIES/LEASING OFFICE ARE OPEN TO THE FLOOR BELOW. | | | THE DESIGN SHALL CONFORM TO SECTION 8.6 VERTICAL | | | OPENINGS AS EITHER A COMMUNICATING SPACE, CONVENIENCE | | | OPENING, ATRIUM, OR MEZZANINE. FOR INSTANCE, EACH | | | OCCUPANT NOT IN THE COMMUNICATING SPACE (SUCH AS | | | AMENITY SECOND FLOOR REST ROOM) NEEDS TO HAVE ACCESS TO | | | AT LEAST ONE EXIT WITHOUT HAVING TO ENTER THE | | | COMMUNICATING SPACE, OR AS A CONVENIENCE OPENING, THE | | | OPENINGS NEED TO BE SEPARATED FROM CORRIDORS. | | | | | | |
|