| Date |
Text |
| 2015-10-20 17:07:34 | PLEASE NOTE THAT THE ELECTRICAL REVIEW OF THE ABOVE | | | MENTIONED JOB HAS BEEN COMPLETED. BELOW ARE THE | | | COMMENTS WITH REGARDS TO THE REQUIRED CORRECTIONS. THE | | | PLANS SHALL BE REVISED TO ADDRESS FOLLOWING ITEMS; ONCE | | | CORRECTED SHALL BE RESUBMITTED FOR ANOTHER REVIEW. | | | PG. E2.1.1 | | | 1. AN ADDITIONAL EXIT LIGHT OR DUAL FACE IS REQUIRED. | | | EXIT LIGHT SHALL BE VISIBLE FROM EITHER PATH OF TRAVEL. | | | 2. REVIEW AND REVISE EXIT LIGHT PLACEMENT IN THE | | | AMENITY & LEASING AREA. FROM THE SUBMITTED DRAWING I | | | CAN?T BE CERTAIN IF ALL DOORS ACTUALLY LEAD TO THE PATH | | | OF EGRESS. | | | PG. E2.1.2 | | | 1. EXIT LIGHT REQUIRED IN THE GARAGE AREA. THIS APPEARS | | | TO BE A HANDICAP RAMP. (N/1) | | | 2. EXIT LIGHT REQUIRED FROM GARAGE. (I-J/14) | | | 3. EXIT LIGHT REQUIRED FROM GARAGE. (A-B/13) WILL | | | COMPARE W/SHEET E4.4 | | | 4. EXIT LIGHT REQUIRED FROM GARAGE. ( H/13-14) ? ? ? ? | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|