| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-03 13:11:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. NARRATIVE REFERS TO REVISION 10 FOR SHEET A3.1.1. I | | | WAS UNABLE TO LOCATE THIS REVISION. | | | | | | SEE NARRATIVE, SHEET A3.1.1, ELIMINATING GUARDRAIL ATOP | | | CONCRETE CRASH WALLS IN GARAGE. AFTER A THOROUGH SEARCH | | | OF THIS PAGE, I WAS UNABLE TO LOCATE A REVISION 10 ON | | | THIS SHEET. PLEASE NOTE THAT IT IS ALSO NOT INCLUDED IN | | | THE REVISION BLOCK. SHEET A3.1.1 SUBMITTED FOR THIS | | | REVISION INCLUDES REVISIONS UP TO REVISION 8. | | | | | | 2. CHANGE IN ELEVATION AT STAIR 3 IS NOT CLEAR. SEE FBC | | | 1003.5 REGARDING CHANGE IN ELEVATION AND PROVIDE A | | | DETAIL WHICH SHOWS COMPLIANCE. | | | | | | 3. SHEET 9.2, REVISION 10 NOT SUBMITTED. | | | | | | 4. ARCHITECT TO CONFIRM THAT ALL FIRE RATED WALLS SHOWN | | | ON PLANS ARE IN PLACE, IN PARTICULAR THE AMENITY AREA, | | | SECOND FLOOR. ALSO SEE MECHANICAL COMMENT REGARDING | | | REMOVAL OF FIRE DAMPER. IT APPEARS THAT THIS FIRE RATED | | | WALL IS REQUIRED, AND THE DAMPER IS REQUIRED. SEE FBC | | | 713.1. PLEASE FEEL FREE TO CONTACT ME TO DISCUSS IF | | | NECESSARY. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|