| Notes |
| Date |
Text |
| 2016-01-20 15:49:53 | 5TH REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15081109 | | | 01/20/16 | | | | | | 1) THE PLANS ARE INDICATING COMBUSTIBLE WOOD DOORS FOR | | | ALL OF THE AC CLOSETS AND MECHANICAL ROOMS. PLEASE | | | REFER TO SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION, | | | AND SECTION 606.2 FBC-14 MECHANICAL AND PROVIDE | | | NON-COMBUSTIBLE DOORS. | | | 2) THE C02 SENSORS ARE NOT UL LISTED AND LABELED. | | | PROVIDE A UL LISTED DEVICE. | | | 3) THE RETURN DUCT FROM THE EMPLOYEE LOUNGE INTO THE | | | MECHANICAL ROOM IS UNDERSIZED PER SECTION 601.5 FBC-14 | | | MECHANICAL. DUCT MUST HAVE A CROSS-SECTION AREA OF 225 | | | SQ. INCHES. | | | 4) THE ENERGY CALCULATION FORM 506-2014 MUST BE REVISED | | | TO SHOW THE CHANGE TO THE SMALLER CAPACITY HEAT PUMPS. | | | 5) PLEASE CLARIFY WHY THE AIR HANDLER CAPACITIES HAVE | | | NOT BEEN REDUCED TO MATCH THE REDUCED HEAT PUMP | | | CAPACITIES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|