2016-01-20 15:49:535TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #15081109
 01/20/16
  
 1) THE PLANS ARE INDICATING COMBUSTIBLE WOOD DOORS FOR
 ALL OF THE AC CLOSETS AND MECHANICAL ROOMS. PLEASE
 REFER TO SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION,
 AND SECTION 606.2 FBC-14 MECHANICAL AND PROVIDE
 NON-COMBUSTIBLE DOORS.
 2) THE C02 SENSORS ARE NOT UL LISTED AND LABELED.
 PROVIDE A UL LISTED DEVICE.
 3) THE RETURN DUCT FROM THE EMPLOYEE LOUNGE INTO THE
 MECHANICAL ROOM IS UNDERSIZED PER SECTION 601.5 FBC-14
 MECHANICAL. DUCT MUST HAVE A CROSS-SECTION AREA OF 225
 SQ. INCHES.
 4) THE ENERGY CALCULATION FORM 506-2014 MUST BE REVISED
 TO SHOW THE CHANGE TO THE SMALLER CAPACITY HEAT PUMPS.
 5) PLEASE CLARIFY WHY THE AIR HANDLER CAPACITIES HAVE
 NOT BEEN REDUCED TO MATCH THE REDUCED HEAT PUMP
 CAPACITIES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER