| Plan Review Notes For Permit 15081109 |
| Permit Number |
15081109 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-12-18 07:24:19 | 3RD REVIEW 2014 MECHANICAL | | | PERMIT #15081109 | | | 12/18/15 | | | | | | 1) AS PREVIOUSLY NOTED IN THE 2ND REVIEW, THE AC | | | SYSTEMS CANNOT BE SIZED LARGER THAN THE CALCULATED | | | LOADS. THE TOTAL LOAD CALCULATED BY KO DESIGN FOR | | | COOLING IS 31.56 TONS, HOWEVER THE TOTAL LOAD SHOWN IN | | | THE AC SCHEDULE ON SHEET M1 IS 51.66. PLEASE SEE | | | SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. | | | 2) THE LOCATIONS OF THE DUCT SMOKE DETECTORS SHOWN ON | | | THE REVISED PLANS ARE NOT IN COMPLIANCE WITH 606.2.1 | | | FBC-14 MECHANICAL: THE DEVICES SHALL BE UPSTREAM OF THE | | | O/A DUCT CONNECTIONS INTO THE RETURN AIR PLENUMS. | | | 3) THE FLEX DUCTS CANNOT BE USED FOR OUTSIDE AIR DUCTS | | | BECAUSE THEY ARE NOT MOISTURE RESISTANT- PROVIDE METAL | | | DUCTING. | | | 4) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE | | | COOKTOP DO NOT INDICATE THE PRODUCT IS LISTED AND | | | LABELED IN ACCORDANCE WITH UL 197 FOR COMMERCIAL USE. - | | | SEE SECTION 917.1 FBC-14 MECHANICAL AND PROVIDE | | | DOCUMENTION VERIFYING COMPLIANCE. | | | 5) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | CO2 SENSORS REVIEWED AND APPROVED BY THE ENGINEER OF | | | RECORD. | | | 6) PLACE NOTE ON THE PLAN THE KITCHEN GAS RANGE, | | | ELECTRIC COOKTOP AND HOOD WILL BE DONE UNDER SEPARATE | | | PERMIT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|