2015-12-18 07:24:193RD REVIEW 2014 MECHANICAL
 PERMIT #15081109
 12/18/15
  
 1) AS PREVIOUSLY NOTED IN THE 2ND REVIEW, THE AC
 SYSTEMS CANNOT BE SIZED LARGER THAN THE CALCULATED
 LOADS. THE TOTAL LOAD CALCULATED BY KO DESIGN FOR
 COOLING IS 31.56 TONS, HOWEVER THE TOTAL LOAD SHOWN IN
 THE AC SCHEDULE ON SHEET M1 IS 51.66. PLEASE SEE
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
 2) THE LOCATIONS OF THE DUCT SMOKE DETECTORS SHOWN ON
 THE REVISED PLANS ARE NOT IN COMPLIANCE WITH 606.2.1
 FBC-14 MECHANICAL: THE DEVICES SHALL BE UPSTREAM OF THE
 O/A DUCT CONNECTIONS INTO THE RETURN AIR PLENUMS.
 3) THE FLEX DUCTS CANNOT BE USED FOR OUTSIDE AIR DUCTS
 BECAUSE THEY ARE NOT MOISTURE RESISTANT- PROVIDE METAL
 DUCTING.
 4) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE
 COOKTOP DO NOT INDICATE THE PRODUCT IS LISTED AND
 LABELED IN ACCORDANCE WITH UL 197 FOR COMMERCIAL USE. -
 SEE SECTION 917.1 FBC-14 MECHANICAL AND PROVIDE
 DOCUMENTION VERIFYING COMPLIANCE.
 5) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CO2 SENSORS REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD.
 6) PLACE NOTE ON THE PLAN THE KITCHEN GAS RANGE,
 ELECTRIC COOKTOP AND HOOD WILL BE DONE UNDER SEPARATE
 PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER