| Plan Review Notes For Permit 15081109 |
| Permit Number |
15081109 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-01-16 10:24:38 | 3RD REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 2NDREQUEST ON COMMENTS 1-4 / 3RDREQUEST ON COMMENT 5 | | | | | | 1. SHOW LINE PRESSURE UPSTREAM AND DOWN STREAM OF | | | STEPDOWN REGULATORS. PER WPB AMEND.TO FBC SEC 107.2.1 | | | 2. 25 EHD IS UNDERSIZED ON GENERATOR PER TABLE402.4(15) | | | 3.18 EHD IS UNDERSIZED ON SIX BURNER RANGE PER TABLE | | | 402.(15) | | | 4. SIZE PIPE ON DOWN STREAM SIDE OF STEPDOWN REGULATORS | | | ON ALL APPLIANCES.PER WPB AMEND.TO FBC SEC 107.2.1 | | | 5. 1ST REVIEW REFERENCES COMBUSTION AIR BUT I DID NOT | | | SEE ANY CALCS PLEASE CLARIFY. |
|