Plan Review Notes
Plan Review Notes For Permit 15081109
Permit Number 15081109
Review Stop P
Sequence Number 2
Notes
Date Text
2015-11-06 11:24:171) SHT. FP-1 - THE BREAK ROOM SINK SHALL COMPLY WITH
 2014 FBC-ACCESSIBILITY SECS. 212, 212.3, 804. SHOW
 COMPLIANCE ON THE PLANS. THERE ARE NO HEIGHT
 MEASUREMENTS SHOWN ON THE ELEVATION DETAILS SO
 COMPLIANCE WITH THE FL. ACCESSIBILITY CODE COULD NOT BE
 CONFIRMED. ALSO, SHOW THE CLEAR FLOOR SPACES AT
 APPLIANCES AND FIXTURES PER THE FBC-ACCESSIBILITY SECS.
 305 & 306.THE MAXIMUM COUNTER HEIGHT SHALL BE 34 INCHES
 PER FAC SEC. 606.3. THE DRYER SHALL COMPLY WITH SEC.611
 OF THE FBC-ACCESSIBILITY.
 2) THE RANGE IN THE BREAKROOM SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS. 305, 804.6.4 -804.6.5.3. SHOW
 COMPLIANCE ON THE PLANS.THE MAXIMUM COUNTER HEIGHT
 SHALL BE 34 INCHES.
 3) A SERVICE SINK IS REQUIRED PER 2014 FBC-PLUMBING
 TABLE 403.1. SHOW THE LOCATION OF THE SERVICE SINK ON
 THE FLOOR PLAN AND THE SANITARY AND WATER RISERS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT AN ENLARGED FLOOR PLAN OF THE TOILET ROOMS
 AND SHOW THE CLEAR INSIDE DIMENSIONS OF THE TOILET
 ROOMS, SHOWER, FIXTURE CLEARANCES, ETC. ALL TOILET
 ROOMS & BATHING ROOMS SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SEC.213.604, 606, 608.THE MINIMUM
 WIDTH OF A SINGLE USER TOILET ROOM SHALL BE 85 INCHES
 IF BUILT PERFECT; 86 INCHES ALLOWS FOR TOLERANCES. SEE
 TOILET ROOMS # 104 & 105.
 5) SUBMIT ELEVATION DETAILS FOR ALL HANDICAP ACCESSIBLE
 FIXTURES, GRAB BARS, SHOWER CONTROLS, ETC.SHOW ALL
 MEASUREMENTS FROM THE FINISHED FLOOR TO THE TOP OF THE
 GRAB BARS, THE DISTANCE FROM ADJACENT WALLS,
 ETC.FBC-ACCESS SECS.604.2,609.
 6)THE FIRST FLOOR SANITARY SYSTEM DESIGN FOR TOILET
 ROOMS #104, 105 AND THE SECOND FLOOR DOES NOT COMPLY
 WITH SEC. 912.1 FOR WET VENTING. WET VENTED FIXTURES IN
 BATHROOM GROUPS SHALL BE LOCATED ON THE SAME FLOOR. AS
 DRAWN, THERE ARE WATER CLOSETS ON THE FIRST FLOOR BEING
 WET VENTED BY FIXTURES ON THE SECOND FLOOR AND THE
 DRINKING FOUNTAINS ARE INSTALLED ON THE WET VENT WHICH
 IS NOT PERMITTED.
 7) THE HIGH UNIT OF THE DRINKING FOUNTAINS WILL
 PROBABLY REQUIRE A CANE TOUCH SKIRT TO COMPLY WITH
 FBC-ACCESSIBILITY SEC.307.2 FOR THE PROTRUDING OBJECTS
 GUIDELINES.
 8) THE SHOWER IN THE STUDIO BATHROOM #116 C SHALL
 COMPLY WITH THE FBC- ACCESSIBILITY SECS.213.3.6 &
 608.2.1.THE SHOWER DIMENSIONS SHALL BE 36" X 36" FOR A
 TRANSFER TYPE SHOWER.THESE DIMENSIONS ARE ABSOLUTE AND
 ARE NOT MINIMUMS.
 9) SHT. P-3 - THE WET VENT FOR THE WATER CLOSET IN ROOM
 # 116 C AND ROOM #122 DOES NOT COMPLY WITH 2014
 FBC-PLUMBING SEC.912 FOR A HORIZONTAL WET VENT.THE
 DRINKING FOUNTAINS IN THE BATHROOM LOBBY AND THE STUDIO
 KITCHEN SINK SHALL CONNECT TO THE HORIZONTAL DRAIN
 DOWNSTREAM OF THE WET VENT.
  
 PLEASE CALL ME TO SET UP AN APPOINTMENT TO REVIEW THE
 COMMENTS.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  