| 2015-11-12 17:39:27 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15081109 |
| | 11/12/15 |
| | |
| | 1) REFER TO SECTION C403.2.2 FBC-14 ENERGY |
| | CONSERVATION: THE OUTPUT CAPACITIES OF THE AC SYSTEMS |
| | IN THE EQUIPMENT SCHEDULE ON SHEET M1 ARE EXCEEDING THE |
| | CALCULATED LOADS SHOWN IN THE CALCULATION SUBMITTAL |
| | FROM K.O. ENERGY DESIGN. A) SYSTEM 1 CALCULATIONS |
| | INDICATE 12.82 TONS COOLING , SYSTEM 1 SCHEDULE |
| | INDICATES 21.5 TONS. B) SYSTEM 2 CALCS- 7.97 TONS, |
| | SCHEDULE- 12.5 TONS. C) SYSTEM 3 CALCS- 10.78, |
| | SCHEDULE- 19.5 TONS. TOTAL COOLING CALCULATION- 31.56 |
| | TONS, TOTAL COOLING SHOWN ON SCHEDULE- 53.5 TONS. |
| | PLEASE NOTE THAT THE CALCS SHOW 0 BTUH FOR HEATING |
| | REQUIRED, HOWEVER HEATING IS REQUIRED PER SECTION 309.1 |
| | FBC-14 MECHANICAL. |
| | 2) SHEET M1 & M2: REFER TO TABLE 404.4 FBC-14 |
| | MECHANICAL- THE OUTSIDE AIR CALCULATIONS MUST BE |
| | REVISED TO INCLUDE THE GALLERY AREAS AT 7.5 CFM PER |
| | PERSON AND THE THEATER AREA AT 10 CFM PER PERSON. |
| | FURTHER REVISION MAY BE REQUIRED PENDING OCCUPANCY |
| | CLASSIFICATION CHANGES. |
| | 3) M1: THE FIRST FLOOR STUDIO BATHS INDICATES A SHOWER |
| | WHICH REQUIRES 50 CFM EXHAUST IN ADDITION TO THE 50 CFM |
| | FOR THE TOILET- TABLE 403.3. |
| | 4) M1: INDICATE HOW THE RETURN AIR SYSTEM IS |
| | FUNCTIONING FOR AHU #7. |
| | 5) M1: PROVIDE ADDITIONAL DETAILS TO CLARIFY HOW |
| | OUTSIDE AIR IS BEING SUPPLIED FOR AHU'S 3, 4, 5, 6, 7, |
| | 14, AND 15. PROVIDE THE SIZES OF THE W.P. WALL JACKS, |
| | SHOW THE REQUIRED MOTORIZED DAMPERS FOR THE INTAKES, |
| | AND INDICATE THE AMOUNT OF O/A BEING SUPPLIED. REFER TO |
| | SECTION 401.4 AND 401.5 FOR AIR INTAKE COMPLIANCES- |
| | PLEASE NOTE THAT THE OPENINGS SHALL BE LOCATED A |
| | MINIMUM OF 10' |
| | HORIZONTALLY FROM ALLEYS UNLESS THEY ARE 25' ABOVE |
| | GRADE. |
| | 6) M1: REFER TO SECTION 3006.2 FBC-14 BUILDING AND |
| | CLARIFY IF THE ELEVATOR ROOM CONTAINS SOLID STATE |
| | EQUIPMENT WHICH REQUIRES AN INDEPENDENT AC SYSTEM. SEE |
| | ALSO SECTION 3006.4 FOR FIRE BARRIER ENCLOSURE- NOTE: |
| | FIRE DAMPERS MAY BE REQUIRED FOR THE DUCTS PENETRATING |
| | THE ELEVATOR ROOM CEILING. |
| | 7) M1: PROVIDE A DETAIL FOR FIRE DAMPERS IN THE |
| | STAIRWELL CEILINGS- SEE SECTION 717.6.2: A SHAFT |
| | ENCLOSURES OR CEILING RADIATION DAMPERS ARE REQUIRED. |
| | REFER TO SECTION 1022.5 & 1022.6 FBC-14 BUILDING: |
| | INDEPENDENT VENTILATION SYSTEMS FOR INTERIOR EXIT |
| | STAIRWAYS ARE REQUIRED- THE SUPPLY DUCTS PENETRATING |
| | INTO THE STAIRWELLS ARE NOT PERMITTED. |
| | 8) M1 & M2: SHOW THE LOCATIONS OF THE REQUIRED DUCT |
| | SMOKE DETECTORS IN THE AHU RETURN AIR SYSTEMS- SECTION |
| | 606.2.1. |
| | 9) M2: INDICATE HOW THE RETURN AIR SYSTEM IS |
| | FUNCTIONING FOR AHU-13. NO ACCESS FOR RETURN AIR INTO |
| | THE MECHANICAL ROOM IS SHOWN ON THE PLAN. |
| | 10) THE LOCATION OF THE HOOD EXHAUST TERNINATION IS |
| | REQUIRED TO BE 10' ABOVE GRADE AND 10' FROM THE |
| | PROPERTY LINE- SECTION 501.3.1 FBC-14 MECHANICAL: THE |
| | PLAN DOES NOT CLEARLY INDICATE COMPLIANCE. SUBMIT |
| | MANUFACTURER'S SPECS FOR THE GAS GRILL IN THE KITCHEN. |
| | PLEASE NOTE A GREASE HOOD AND FIRE SUPPRESSION MAY BE |
| | REQUIRED. |
| | 11) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW PROVIDE |
| | AN AIR BALANCE CALCULATION ON THE PLAN. |
| | 12) AS PREVIOUSLY NOTED IN THE 1ST REVIEW, DEMAND |
| | CONTROLLED VENTILATION IS REQUIRED FOR THE PROPOSED |
| | OCCUPANCY PER SECTION C403.2/.5.1 FBC-14 ENERGY |
| | CONSERVATION- SEE SECTION 202 DEFINITIONS AND PROVIDE A |
| | SYSTEM CAPABILITY ON THE PLANS. NOTE: TYPICALLY THIS IS |
| | ACCOMPLISHED THROUGH THE USE OF SENSORS AND PROGRAMMING |
| | OF THE SYSTEMS |
| | 13) DEFERRED SUBMITTALS: FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. SUBMITTALS SHALL |
| | INCLUDE THE FIRE DAMPERS, DUCT SMOKE DETECTORS, AIR |
| | INTAKE AND EXHAUST LOUVERS, WALL AND ROOF JACKS, DCV |
| | SENSORS, AND AC SYSTEMS. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. |
| | A) PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |