Plan Review Notes
Plan Review Notes For Permit 15081109
Permit Number 15081109
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2015-11-05 07:53:2311/5/15, LINDOW
  
 PROVIDE ENGINEER OF RECORD STAMP FOR FIRE SPRINKLER
 DRAWINGS.
 SHOP DRAWINGS REQURED FOR FIRE SPRINKLER.
 FIRE SPRINKLER DRAWINGS SHOW WRONG EDITION OF THE CODE,
 SHOULD BE 2010.
 FIRE ALARM SYSTEM REQUIRED TO MONITOR FIRE SPRINKLER.
 PROVIDE PROTECTION TO COMPLY WITH NFPA 96 FOR STOVE IN
 KITCHEN.