| 2015-11-19 12:27:14 | BUILDING PLAN REVIEW |
| | W.P.B. PERMIT:15081109- MASTER BUILD-OUT |
| | W. P. B. PERMIT: 15081111-FOUNDATION |
| | ADD: 444 BUNKER RANCH RD. |
| | CONT: CURY BUILDING & DESIGN |
| | TEL: (561)718-1398 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. NOV. 18/2015 |
| | ACTION: DENIED |
| | |
| | 2ND REQUEST. CONTRACTOR TO BIND ALL PLANS INTO A SET, |
| | CIVIL, SURVEY, ARCHITECTURAL, STRUCTURAL, MECHANICAL, |
| | ELECTRICAL, PLUMBING & FIRE SPRINKLER PLANS COMBINED TO |
| | MAKE ONE SET. AS SUBMITTED IT LOOKS LIKE 4 SETS OF |
| | CIVIL WERE SUBMITTED. AS PLAN REVIEWERS WE USUALLY LOOK |
| | ONLY AT ONE SET OF PLANS, 2 SETS REQUIRED UNLESS THE |
| | PROJECT IS A RESIDENT INSPECTOR OR THRESHOLD BUILDING. |
| | . WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1) 2ND REQUEST. THE RESPONSE INDICATES THE PLANS WERE |
| | DESIGNED UNDER THE 2014 EXISTING BUILDING CODE, THE |
| | PRESCRIPTIVE COMPLIANCE METHOD CHAPTER 4. BOTH THE |
| | COVERSHEET AND S7 BOTH INDICATE A LEVEL II ALTERATION, |
| | THE WORK AREA METHOD OF COMPLIANCE, CHAPTER 8. |
| | |
| | THE PLANS APPEAR THAT THIS ALTERATION IS AT A MINIMUM, |
| | A LEVEL III, 2014 EXST. BLDG CODE 505.1 SCOPE. LEVEL 3 |
| | ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS 50 PER |
| | CENT OF THE AGGREGATE AREA OF THE BUILDING. |
| | THE DEMOLITION PLAN REMOVED ALL NON-BEARING WALLS ON |
| | THE 2 FLOORS. SHEET S2 SHOWS THE CENTER SECTION OF THE |
| | BUILDING BEING REBUILT, SHEET S3 SHOWS FLOOR JOIST |
| | BEING DOUBLED THROUGH |
| | |
| | OUT THE WHOLE OF THE 2ND FLOOR, SHEET S5 SHOWS NEW |
| | ELEVATOR PIT, SHAFT WALLS, THE WHOLE ROOF TRUSS SYSTEM/ |
| | ROOF SHEATHING BEING INSULATED WITH ICYNENE FOAM. A |
| | LEVEL III LIMITED STRUCTURAL ALTERATION 907.4.3. |
| | |
| | COMMENT FROM 1ST REVIEW. SHEET S07 CODE REFERENCE |
| | SHEET. LIST THE 2014, 5TH EDITION OF THE FLORIDA |
| | BUILDING CODE. THE PLANS ARE SILENT TO WHAT DESIGN THE |
| | PLANS WERE DESIGN TO UNDER THE 2014 FBC-EXISTING |
| | BUILDING CODE, 301.1. |
| | |
| | 2) ???????????? SHEET S07 STRUCTURAL NOTES UNDER THE |
| | HEADING OF MATERIALS THE STRENGTH OF CONCRETE IS |
| | DECLARED FOR SLABS, COLUMNS AND BEAMS, SHEET S02 THE |
| | COLUMN SCHEDULE UNIT C6 IS FILLED CELL MASONRY THE |
| | PLANS INDICATE THE USE OF 3000 PSI CONCRETE, IN FILED |
| | CELL MASONRY SHOULDN'T THE USE OF GROUT BE USED INSTEAD |
| | OF CONCRETE. ACI 530 1.16.1. & TABLE 1.16.1 GROUTING |
| | MINIMUM SPACES. |
| | |
| | 3) COMPLIED. SHEET S2 FOOTING SCHEDULE FOOTING F2-F6 |
| | INDICATES THE WIDTH & LENGTH OF THE FOOTING BUT NOT THE |
| | HEIGHT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) COMPLIED. SHEET S2 FOOTING SCHEDULE F4 DOES NOT |
| | PROVIDE AT WHAT CENTER TO CENTER IN INCHES WHAT THE |
| | STEEL MATS ARE TO BE INSTALLED. 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 5) SHEET S-7 INDICATES THE PLANS WERE DESIGNED TO THE |
| | 2014 FBC-B AND ASCE 7-10. THE WIND DESIGN CRITERIA IS |
| | NOT PROVIDED. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 5.1.COMPLIED. ULTIMATE DESIGN WIND SPEED, VULT, |
| | (3-SECOND GUST), MILES PER HOUR (KM/HR) AND NOMINAL |
| | DESIGN WIND SPEED, VASD, AS DETERMINED IN ACCORDANCE |
| | WITH SECTION 1609.3.1. |
| | 5.2. COMPLIED. RISK CATEGORY. |
| | 5.3.COMPLIED. WIND EXPOSURE. APPLICABLE WIND DIRECTION |
| | IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. |
| | 5.4. COMPLIED. APPLICABLE INTERNAL PRESSURE |
| | COEFFICIENT. |
| | 5.5.SEMI-COMPLIED. DESIGN WIND PRESSURES TO BE USED FOR |
| | EXTERIOR COMPONENT AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE |
| | STRUCTURE, PSF (KN/M2).SHEETS S1-S6 DEAL WITH THE WIND |
| | PRESSUE |
| | |
| | |
| | |
| | 6) 2ND REQUEST. SHEET S7 & S1. MEAN ROOF HEIGHT GIVEN |
| | 27?-10?. SHEET S1 ELEVATIONS WITH PRESSURES. |
| | |
| | 6A) ES WINDOWS SERIES ?1500? NOA. 14-0923.08 WILL NEED |
| | TO IDENTIFY EITHER A/C OR B/C TYPE OF FASTENERS. NOTE |
| | WINDOW TYPE 6 FOR EXAMPLE (3) 4?X7? WINDOWS 48?X 84?. |
| | A/C TYPE FASTENERS ARE ONLY GOOD FOR +/- 36 PSF. IF B/C |
| | TYPE OF FASTENER IS USED, GOOD FOR ALL TYPE OF |
| | INSTALLATIONS. PLEASE IDENTIFY FASTENER TYPE. |
| | |
| | 6B) ES WINDOWS TUBE MULLION NOA 14-0731.06 WILL NEED TO |
| | IDENTIFY ANCHOR TYPES, SOME TYPES OF ANCHORS HAVE LOW |
| | PRESSURES. IDENTIFY WINDOW DIMENSIONS AND MULLION SIZES |
| | AND LENGTH. |
| | |
| | 6C) E S WINDOWS SERIES 9000 ALUMINUM OUTSWING FRENCH |
| | DOORS NOA 130617.29 PRESSURES ARE GOOD. |
| | 6C)(1) SHEET S1 FRONT ENTRY DOOR, NORTH ELEVATION(A) IS |
| | INDICATED AS 9?-4? WIDE. TYPO? THERE IS NO DOOR FRAME |
| | THAT WIDE IN THE PRODUCT APPROVAL REPORT. |
| | 6C)(2) SHEET S1 SOUTH ELEVATION DOOR C IS INDICATED AS |
| | 5?-8? WIDE. SHEET L1 INDICATES THIS SET OF DOORS IS |
| | EXIT # 4. THE 2014 FBC-B 1008.1.1 SIZE OF DOOR IS 32 |
| | INCHES CLEAR OPENING MEASURED FROM FACE OF DOOR TO |
| | OPPOSITE STOP WHEN THE DOOR IS OPEN AT 90 DEGREES. |
| | |
| | 7) SEE COMMENT 5.5 .SHEET S7 & S4. PROVIDE THE MEAN |
| | ROOF HEIGHT AND SECTION THROUGH THE ROOF WITH ELEVATION |
| | OF ROOF AND OF THE PARAPET. THE MEAN ROOF HEIGHT CAN |
| | NOT BE DETERMINED , NOR CAN THE PRESSURES FOR ROOF |
| | ZONES, NOTE THE PRESSURES ARE ASSUMED TO BE VASD? 2014 |
| | FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS FOR BUILDING |
| | HEIGHT AND EXPOSURE. |
| | |
| | 8)BUILDING PROVISO/ 107.3.4.2 DEFERRED SUBMITTALS: |
| | MISSING PRODUCT APPROVALS: 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS FOR EXHAUST |
| | FANS AND A/C ROOF TOP DOWN UNITS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 9)BUILDING PROVISO: 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10) TODATE THERE HAVE BEEN NO FIRE PROTECTION PLANS |
| | SUBMITTED. |
| | |
| | 10A) 2ND REQUEST. SEE MECHANICAL RESPONSE AS TO |
| | LOCATION OF EXHAUST FROM KITCHEN HOOD, THERE MAYBE |
| | STILL ISSUES AS TO WHERE THE FINAL LOCATION OF THE HOOD |
| | EXHAUST. SHEET S3 ROOF FRAMING PLAN DOES NOT PROVIDE A |
| | SECTION FOR THE ROOF FRAMING AND HEADER FOR THE NEW |
| | EXHAUST VENT THAT WILL GO THROUGH THE ROOF FRAMING AND |
| | SHEATHING. NOTE THERE IS ALSO NO ROOF TOP CURB DETAIL, |
| | HOW IT IS TO BE ANCHORED TO THE ROOF FRAMING. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 10B) MAY STILL HAVE ISSUES DEPENDING ON THE HOOD |
| | EXHAUST LOCATION. WITH THE LOCATION OF THE EXHAUST FAN |
| | NOT PROVIDED NOR THE HEIGHT OF THE PARAPET PLEASE SHOW |
| | COMPLIANCE WITH 2014 FBC-B 1013.6 MECHANICAL EQUIPMENT. |
| | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | COMPLIED. 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED |
| | WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET |
| | (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| | SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| | 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE |
| | BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| | THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER. |
| | |
| | 10C) MAY STILL HAVE ISSUES DEPENDING ON THE HOOD |
| | EXHAUST LOCATION. PLEASE REVIEW THE REQUIREMENTS FOR |
| | SCREENS FOR MECHANICAL EQUIPMENT. 1509.6 MECHANICAL |
| | EQUIPMENT SCREENS. MECHANICAL EQUIPMENT SCREENS SHALL |
| | BE CONSTRUCTED OF THE MATERIALS SPECIFIED FOR THE |
| | EXTERIOR WALLS IN ACCORDANCE WITH THE TYPE OF |
| | CONSTRUCTION OF THE BUILDING. WHERE THE FIRE SEPARATION |
| | DISTANCE IS GREATER THAN 5 FEET (1524 MM), MECHANICAL |
| | EQUIPMENT SCREENS SHALL NOT BE REQUIRED TO COMPLY WITH |
| | THE FIRE-RESISTANCE RATING REQUIREMENTS. |
| | |
| | 11)2ND REQUEST. SHEET L1 & L2 SHOWS A 1 HOUR WALL AND |
| | INTERIOR PARTITION FILE NUMBER GA FILE WP 1072. |
| | THERE ARE NO CUT SECTIONS THROUGH THE STAIRWELL |
| | PROVIDING HOW THE WOOD FRAMING MEMBERS FOR THE 2ND |
| | FLOOR SYSTEM AND ROOF SYSTEM ARE TO BE INCORPORATED |
| | INTO THE SHAFT WALL CONSTRUCTION. 2010 FBC-B 713.8 |
| | PENETRATIONS. STRUCTURAL ELEMENTS, SUCH AS BEAMS OR |
| | JOIST WHERE PROTECTED IN ACCORDANCE WITH 714 SHALL BE |
| | PERMITTED TO PENETRATE A SHAFT ENCLOSURE. PLEASE |
| | PROVIDE ADDITIONAL INFORMATION FOR CODE COMPLIANCE. |
| | |
| | 11B) SHEET S6 EAST STAIR 2/S6. THIS STAIR SHOWS A RISER |
| | # 24 THAT IS ABOVE THE FINISH FLOOR LEVEL. RISER # 24 |
| | IS ALSO A THIRD LARGER THAN THE REST OF THE RISERS |
| | 1009.7.4 DIMENSIONAL UNIFORMITY. |
| | THIS SAME DETAIL SHOWS A 18X18 RATED DAMPER FOR THE |
| | SECOND FLOOR CEILING AND DIRECTED TO THE FLOOR. THE |
| | PLANS ALSO SHOW A 12X12 RAG NO DAMPER. |
| | |
| | 11C) BOTH THE EAST AND WEST STAIR SHOW ON M2 SUPPLY |
| | DUCTS INTO BOTH STAIRWELLS. 2014 FBC-B 1022.5 |
| | PENETRATIONS . PENETRATIONS ARE PROHIBITED EXCEPT FOR |
| | REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY |
| | FOR INDEPENDENT VENTILATION OR PRESSURIZATION OF THE |
| | STAIRWELL. |
| | |
| | 11D) SHEET L2 EAST STAIRWELL THE 2ND FLOOR LANDING |
| | SHOWS A DOOR IN THE STAIRWELL THAT OPENS INTO A |
| | MECHANICAL ROOM. 2014 FBC-B 1022.5 PENETRATIONS . |
| | PENETRATIONS ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS. DOORS THAT LED INTO STAIRWELLS HAVE TO BE FROM |
| | HABITABLE SPACES, EGRESS DOORS ONLY! |
| | |
| | 11E) SHEET S6 BOTH THE EAST AND WEST STAIR ENCLOSURE |
| | ONLY SHOW A HANDRAIL ONLY ON ONE SIDE. 2014 FBC-B |
| | 1009.15. HAND RAILS ARE REQUIRED ON BOTH SIDES. |
| | |
| | COMMENT 1ST REVIEW. SHEET L1 & L2 WHAT APPEARS TO BE |
| | FIRE RATED VERTICAL EXIT STAIRS NEITHER LIFE SAFETY |
| | SHEET DO NOT PROVIDE WALL IDENTIFICATION TAGS SHOWING |
| | THE TYPE OF WALL OR IF FIRE RATINGS, MISSING UL LISTING |
| | OF STAIR ENCLOSURE. 2014 FBC-B 1023.3 CONSTRUCTION. |
| | 1023.6 PENETRATIONS. GUARDS |
| | |
| | 12 IN REVIEWING THE PROPOSED USE OF THIS STRUCTURE AND |
| | THE LETTER FROM BETH DEWOODY STATING THE USE WOULD BE |
| | FOR STORAGE PRIVATE DISPLAY FACILITY FOR PERSONAL ART |
| | AND FURNITURE COLLECTION THAT WILL NOT BE OPEN TO THE |
| | PUBLIC. THE DESIGNER OF RECORD HAS NOT GIVEN A PROPOSED |
| | OCCUPANT LOAD. HE HAS GIVEN US THE FORMULAS IN THE CODE |
| | FOR A BUSINESS OCCUPANCY. NOT THE RESTRICTED OCCUPANCY |
| | THAT MS. DEWOODY HAS INDICATED WITHIN THE LETTER |
| | PROVIDED TO STAFF. IT APPEARS NOT ONLY IS THERE A |
| | UNKNOWN OCCUPANT LOAD FOR THE BUILDING, BUT THE A/C |
| | EQUIPMENT FOUND IN THE EQUIPMENT SCHEDULE SHEET M1 |
| | EXCEEDS THE CALCULATED LOADS IN THE CALCULATIONS |
| | SUBMITTED FROM KO ENERGY DESIGN A DIFFERENCE OF 21.94 |
| | TONS. WE ARE VERY CONCERNED THAT THIS MAY BECOME AN A3 |
| | ART GALLERY VERY QUICKLY. WE WILL NEED A DATED LETTER |
| | FROM MS. DEWOODY PROVIDING THE EXPLICIT USAGE OF THIS |
| | SITE WILL BE IF THERE WILL EVER BE ART VIEWINGS TO THE |
| | PUBLIC, FOR BY INVITATION ONLY, GALAS OR PARTIES TO |
| | OCCUR AT THIS LOCATION. THE OWNER HAS ELECTED NOT TO |
| | OPEN THE BUILDING TO THE PUBLIC. ON THE CERTIFICATE OF |
| | COMPLETION THERE WILL BE A VERY RESTRICTIVE CLAUSE AS |
| | TO USE. |
| | |
| | 1ST COMMENTS. SHEET L1 & L2 THERE IS NO DOOR SCHEDULE |
| | TO BE ABLE TO IDENTIFY DOOR OPENINGS. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. 107.3.5.1.1 MINIMUM |
| | PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. |
| | |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | CONSTRUCTION REQUIREMENTS |
| | |
| | 13) 2ND REQUEST. THE 2ND REVIEW THERE 2 SHEETS |
| | SUBMITTED FP1 & FP2 WHICH ARE DETAILS SHOWING |
| | ACCESSIBLE ELEMENTS. NONE OF THESE ELEMENTS ARE |
| | DIMENSIONED TO SHOW CODE COMPLIANCE. THERE ARE NO |
| | DETAILS FOR VERTICAL ACCESSIBILITY/ ELEVATOR |
| | REQUIREMENTS AND SIGNAGE. |
| | |
| | PLEASE PROVIDE DETAILS FOR THE ACCESSIBLE RESTROOMS |
| | SHOW COMPLIANCE WITH 107.3.5.1.1 MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS. ACCESSIBILITY |
| | REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | VERTICAL ACCESSIBILITY 2014 FL ACCESS CODE SECTION 407 |
| | ELEVATOR |
| | TOILET AND BATHING FACILITIES 2014 FL ACCESS CODE |
| | CHAPTER 6 |
| | DRINKING FOUNTAINS 2014 FL ACCESS CODE 602 |
| | SINKS -BREAK ROOM AREAS. 2014 FL ACCESS CODE 606.(1-5). |
| | KITCHENS AND KITCHENETTES 2014 FL ACCESS CODE 804 |
| | |
| | 14) 2ND REQUEST. SHEET LS2 INDICATES A THEATER IN ROOM |
| | 210 PLEASE PROVIDE ADDITIONAL DETAILS, SEAT LAYOUT. |
| | THIS REVIEW THERE IS A SEATING LAYOUT BUT NO THOUGHT |
| | WAS GIVEN TO 2014 FL. ACCESS. CODE FOR COMPANION |
| | SEATING. 802.3. |
| | |
| | 15) SHEET S6 SHOWS THE USE OF SPRAYED IN ICYNENE ROOF |
| | INSULATION TO A VALUE OF R-20. THE PLANS APPEAR NOT TO |
| | HAVE A CEILING BUT A OPEN RAFTER CONCEPT. PLEASE |
| | PROVIDE COMPLIANCE WITH 2014 FBC-B 2603.4 THERMAL |
| | BARRIER OR AN EXCEPTION. THE PLEASE PROVIDE THE TESTING |
| | FOR ICYNENE FOR USE AND LIMITATIONS. |
| | |
| | 16) THE ENERGY CALCULATIONS ALSO SHOW THE USE OF ? INCH |
| | ISO BETWEEN FURRING STRIPS @ 24 INCHES ON CENTER AND |
| | USE OF 5/8 GYPSUM, PLEASE PROVIDE THE SHEET AND DETAIL |
| | WHERE THIS INSTALLATION CAN BE FOUND IN THE PLANS. |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |