| Date |
Text |
| 2015-09-01 10:13:57 | 1) SHT. FP-1 - THE BREAK ROOM SINK SHALL COMPLY WITH |
| | 2014 FBC-ACCESSIBILITY SECS. 212, 212.3, 804. SHOW |
| | COMPLIANCE ON THE PLANS. |
| | 2) THE RANGE IN THE BREAKROOM SHALL COMPLY WITH 2014 |
| | FBC-ACCESSIBILITY SEC.804.6.4 -804.6.5.3. SHOW |
| | COMPLIANCE ON THE PLANS. |
| | 3) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS |
| | OCCUPANCY PER THE 2014 FBC-PLUMBIING TABLE 403.1.THIS |
| | IS NOT A RESTAURANT AND THE EXCEPTION FOR NOT PROVIDING |
| | A DRINKING FOUNTAIN IS FOR RESTAURANTS ONLY PER 2014 |
| | FBC -PLUMBING SEC.410.3. A MINIMUM OF TWO DRINKING |
| | FOUNTAINS ARE REQUIRED PER 2014 FPC TABLE 403.1, |
| | FOOTNOTE # (E) & 2014 FAC SEC.211.2. |
| | 4) A MINIMUM OF 3 WATER CLOSETS FOR THE MALES AND 3 |
| | WATER CLOSETS FOR THE FEMALES ARE REQUIRED FOR AN |
| | OCCUPANT LOAD OF 200 PER THE 2014 FBC-PLUMBING TABLE |
| | 403.1. |
| | 5) A SERVICE SINK IS REQUIRED PER 2014 FBC-PLUMBING |
| | TABLE 403.1. SHOW THE LOCATION OF THE SERVICE SINK ON |
| | THE FLOOR PLAN AND THE SANITARY AND WATER RISERS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 6) SUBMIT AN ENLARGED FLOOR PLAN OF THE TOILET ROOMS |
| | AND SHOW THE CLEAR INSIDE DIMENSIONS OF THE TOILET |
| | ROOMS, SHOWER, FIXTURE CLEARANCES, ETC. ALL TOILET |
| | ROOMS & BATHING ROOMS SHALL COMPLY WITH 2014 |
| | FBC-ACCESSIBILITY SEC.213.604, 606, 608. |
| | 7) SUBMIT ELEVATION DETAILS FOR ALL HANDICAP ACCESSIBLE |
| | FIXTURES, GRAB BARS, SHOWER CONTROLS, ETC.SHOW ALL |
| | MEASUREMETS FROM FINISH FLOOR.WPB AMEND. TO 2014 FBC |
| | SEC. 107.2.1. |
| | 8) SHT. P-2 SHOWS 2 WATER LINES TO A WATER METER. |
| | INDDICATE ON THE PLANS IF THERE ARE TTWO SEPARATE WATER |
| | METERS SERVING THIS PROPERTY OR IF THESE TWO LINES ARE |
| | INTERCONNECTED AND CONTINUE TO CONNECT TO ONE METER. IF |
| | THEY ARE INTERCONNECTED, SHOW ALL THE PIPING TO THE |
| | POINT OF INTERCONNECTION.WPB AMEND TO FBC SEC. 107.2.1. |
| | 9) THE FIRST FLOOR SANITARY SYSTEM DESIGN FOR TOILET |
| | ROOMS #104, 105 AND THE SECOND FLOOR DOES NOT COMPLY |
| | WITH SEC. 912.1 FOR WET VENTING. WET VENTED FIXTURES IN |
| | BATHROOM GROUPS SHALL BE LOCATED ON THE SAME FLOOR. AS |
| | DRAWN, THERE ARE WATER CLOSETS ON THE FIRST FLOOR BEING |
| | WET VENTED BY FIXTURES ON THE SECOND FLOOR. |
| | 10) THE DISHWASHER SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THE 2014 FBC-PLUMBING SEC.802.1.6. |
| | 11) SHT. P-3 - SUBMIT 2 COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR ALL GAS |
| | APPLIANCES/EQUIPMENT.APPLIANCES/EQUIPMENT SHALL BE |
| | LISTED AND LABELED PER 2014 FBC-GAS CODE, SEC.301.3. |
| | 12) THE GAS GENERATOR SHALL COMPLY WITH NFPA 37 AND |
| | COMPLY WITH UL 2200. 2010 FGC SEC.616.1. |
| | 13) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC-2014 FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. |
| | 14) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | 15) SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS |
| | SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(37). |
| | 16) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE |
| | SEC. 402.4.1. |
| | 17) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2014 FUEL GAS CODE SEC. 304. |
| | 18) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | 19) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS |
| | CODE SEC. 502 THRU 505. |
| | 20) SHT. P-4 - OVERFLOW SCUPPERS SHALL BE LOCATED NO |
| | LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE |
| | FINISHED ROOF SURFACE PER 2014 FBC SEC. 1503.4.2.1.THE |
| | SCUPPER DETAIL SHOWS THE BOTTOM OF THE SCUPPER LEVEL |
| | WITH THE ROOF. |
| | 21) INDICATE ON THE PLAN THAT THE ROOF DRAINAGE AREA |
| | INCLUDES 1/2 OF THE AREA OF ALL VERTICAL WALLS THAT |
| | DIVERT RAINWATER TO THE ROOF. 2014 FBC-P SEC.1106.4. |
| | 22) CLEANOUTS ARE REQUIRED IN THE BASE OF THE RAINWATER |
| | LEADERS. FBC-P SEC. 1101.8. |
| | 23) AN OIL SEPARATOR SHALL BE INSTALLED FOR THE |
| | ELEVATOR PIT IN ACCORDANCE WITH 20144 FPC SEC.1003.4. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |