Plan Review Notes
Plan Review Notes For Permit 15081109
Permit Number 15081109
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-10 09:13:181ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15081109
 9/10/15
  
 1) PROVIDE AC COOLING AND HEATING LOAD CALCULATIONS-
 REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION--
 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 2) PROVIDE ENERGY CALCULATIONS PER SECTION C401.2
 FBC-14 ENERGY CONSERVATION: C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
 2A) REFER TO SECTION C101.5.1.1 ALTERATIONS,
 RENOVATIONS AND BUILDING SYSTEMS. ALTERATIONS,
 RENOVATIONS AND BUILDING SYSTEMS MAY UTILIZE FORM C402.
 FORM C402 CAN BE FOUND IN APPENDIX C.
 3) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE VENTILATION CALCULATIONS FOR ALL ROOMS,
 SPACES, AND AREAS SHOWN ON THE PLANS- SEE TABLE 403.3
 FBC-14 MECHANICAL AND PROVIDE A SCHEDULE ON THE PLAN
 INDICATING THE TOTAL CFM'S OF O/A CFM'S OR EXHAUST
 REQUIRED, AND THE AMOUNTS PROVIDED. PLEASE INCLUDE AN
 AIR BALANCE CALCULATION.
 4) SHEETS M1 & M2: THE PLANS ARE OF INSUFFICIENT
 CLARITY FOR REVIEW AND FOR COMPUTER SCANNING AND
 FILING. THE PRINT ON THE AC EQUIPMENT SCHEDULES, AND
 ALL THE PRINTED NOTES, DETAILS, AND TAGS SHOWN IN THE
 HVAC PLANS ARE EITHER TOO SMALL OR TOO FAINT TO READ-
 REFER TO SECTION 107.2.1 WPB AMENDMENTS TO THE FBC-14
 BUILDING CODE AND ENLARGE AND EMBOLDEN THE PRINT TO
 EXPEDITE THE REVIEW OF THIS PROJECT.
 5) M1 & M2: THE AIR HANDLERS ARE SHOWN IN PLENUM RATED
 CLOSETS WITH DOUBLE DOORS, HOWEVER THERE ARE NO
 ARCHITECTURAL FINISH DETAILS OR A DOOR SCHEDULE ON THE
 PLANS TO VERIFY THE MATERIALS USED ARE PLENUM-RATED:
 REFER TO SECTION 602 FBC-14 MECHANICAL.
 6) M1 & M2: REFER TO SECTION 603.1.1 FBC-14 MECHANICAL
 AND PROVIDE DETAILS AND DIMENSIONS ON THE PLANS TO
 VERIFY COMPLIANCE- 603.1.1 SPACE PROVIDED.
 SUFFICIENT SPACE SHALL BE PROVIDED ADJACENT TO ALL
 MECHANICAL COMPONENTS LOCATED IN OR FORMING A PART OF
 THE AIR DISTRIBUTION SYSTEM TO ASSURE ADEQUATE ACCESS
 FOR (1) CONSTRUCTION AND SEALING IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 603.1 OF THIS CODE; (2)
 INSPECTION; AND (3) CLEANING AND MAINTENANCE. A MINIMUM
 OF 4 INCHES (102 MM) IS CONSIDERED SUFFICIENT SPACE
 AROUND AIR HANDLING UNITS.
 7) PROVIDE AN AIR DISTRIBUTION SCHEDULE LISTING THE
 MAKES, MODELS, AND SIZES OF ALL AC SUPPLY DIFFUSERS AND
 RETURN AIR GRILLS.
 8) INDICATE THE TYPE(S) OF SUPPLY AND RETURN DUCTWORK
 TO BE USED, AND PROVIDE DUCT CONNECTION, HANGING AND
 SUPPORT DETAILS- REFER TO TABLE C403.2.7.2 FBC-14
 ENERGY CONSERVATION.
 9) BATH AND TOILET ROOM EXHAUST: ENLARGE THE DETAILS TO
 CLEARLY SHOW THE EXHAUST FANS, THE TYPES AND SIZES OF
 EXHAUST DUCTS, THE DUCT RUNS, AND TERMINATION
 LOCATIONS. PROVIDE EXHAUST FAN EQUIPMENT SCHEDULES ON
 THE PLANS LISTING THE MAKES AND MODELS, AND EXHAUST CFM
 CAPACITIES.
 10) THE PLAN IS INDICATING A KITCHEN AND A KITCHEN
 EXHAUST HOOD- PLEASE PLACE A NOTE INDICATING THE
 KITCHEN HOOD, EXHAUST, AND FIRE SUPPRESSION SYSTEM WILL
 BE DONE UNDER SEPARATE PERMITS, HOWEVER PLEASE INCLUDE
 THE HOOD MAKEUP SUPPLY AND EXHAUST CFM'S IN THE AIR
 BALANCE CALCULATIONS.
 11) PROVIDE A ROOF PLAN INDICATING THE LOCATIONS OF AND
 CLEARANCE DISTANCES FOR THE KITCHEN EXHAUST FAN, AND
 THE MAKEUP AIR INTAKE FAN. REFER TO SECTION 304.11
 GUARDS AND PROVIDE DETAILS IF APPLICABLE.
 12) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS FOR THE AIR HANDLERS- SEE SECTION 307.
 13) PROVIDE AHRI CERTIFICATES FOR THE NEW HP SYSTEMS.
 14) REFER TO SECTION 301.15 FBC-14 MECHANICAL AND
 PROVIDE TIE-DOWN ENGINEERING FOR THE EXTERIOR
 CONDENSERS. PLEASE INCLUDE THE WIND LOAD DESIGN
 CRITERIA AND WIND PRESSURES ON THE PLAN IN ACCORDANCE
 WITH SECTION 1609 FBC-14 BUILDING- 301.15 WIND
 RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE.
 15) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND SHOW COMPLIANCE- SHUTOFF DAMPER
 CONTROLS.
 16) PROVIDE A DETAIL FOR INSTALLATION OF THE FIRE
 DAMPER FOR THE FLEX DUCT PENETRATING THE FLOOR/CEILING
 ASSEMBLY AT THE STAIRWELL/LIBRARY.
 BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE.
 EXCEPTIONS:
 1. GRAVITY DAMPERS SHALL BE PERMITTED IN BUILDINGS LESS
 THAN THREE STORIES IN HEIGHT.
 2. GRAVITY DAMPERS SHALL BE PERMITTED FOR BUILDINGS OF
 ANY HEIGHT LOCATED IN CLIMATE ZONES 1, 2 AND 3. GRAVITY
 DAMPERS SHALL BE PERMITTED FOR OUTSIDE AIR INTAKE OR
 EXHAUST AIRFLOWS OF 300 CFM (0.14 M3/S) OR LESS.
 17) REFER TO SECTION C403.2.5.1 AND SHOW COMPLIANCE-
 C403.2.5.1 DEMAND CONTROLLED VENTILATION.
 DEMAND CONTROL VENTILATION (DCV) SHALL BE PROVIDED FOR
 SPACES LARGER THAN 500 SQUARE FEET (50 M2) AND WITH AN
 AVERAGE OCCUPANT LOAD OF 25 PEOPLE PER 1000 SQUARE FEET
 (93 M2) OF FLOOR AREA (AS ESTABLISHED IN TABLE 403.3 OF
 THEFLORIDA BUILDING CODE, MECHANICAL) AND SERVED BY
 SYSTEMS WITH ONE OR MORE OF THE FOLLOWING:
 1. AN AIR-SIDE ECONOMIZER;
 2. AUTOMATIC MODULATING CONTROL OF THE OUTDOOR AIR
 DAMPER; OR
 3. A DESIGN OUTDOOR AIRFLOW GREATER THAN 3,000 CFM
 (1400 L/S).
 EXCEPTION: DEMAND CONTROL VENTILATION IS NOT REQUIRED
 FOR SYSTEMS AND SPACES AS FOLLOWS:
 1. SYSTEMS WITH ENERGY RECOVERY COMPLYING WITH SECTION
 C403.2.6.
 2. MULTIPLE-ZONE SYSTEMS WITHOUT DIRECT DIGITAL CONTROL
 OF INDIVIDUAL ZONES COMMUNICATING WITH A CENTRAL
 CONTROL PANEL.
 3. SYSTEM WITH A DESIGN OUTDOOR AIRFLOW LESS THAN 1,200
 CFM (600 L/S).
 4. SPACES WHERE THE SUPPLY AIRFLOW RATE MINUS ANY
 MAKEUP OR OUTGOING TRANSFER AIR REQUIREMENT IS LESS
 THAN 1,200 CFM (600 L/S).
 5. VENTILATION PROVIDED FOR PROCESS LOADS ONLY.
 18) PROVIDE TWO COPIES OF A FL. PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE OUTSIDE AIR INTAKE LOUVERS.
 19) PLEASE NOTE THAT FURTHER COMMENTS MAY FOLLOW
 RE-SUBMITTAL OF RESPONSES AND PLAN REVISIONS FOR ALL
 BUILDING DEPARTMENT REVIEW COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719