| Plan Review Notes For Permit 15081109 |
| Permit Number |
15081109 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-23 18:49:41 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | PG. E.1 | | | 1. YOU ARE MISSING EMERGENCY LIGHTING IN: THE | | | ELECTRICAL ROOM, THE REST ROOMS MECHANICAL ROOM, | | | GALLERY STAIRS AND ART WAREHOUSE. | | | 2. THERE IS A MISSING EXIT LIGHT IN ROOM 211 TOWARDS | | | THE REAR STAIRS. | | | PG. E.2 | | | 1. YOU SHALL ADHERE TO THE MANDATORY LIGHTING CONTROL | | | REQUIREMENTS OF THE 2014 FBC-ENERGY SECTION 505 | | | | | | IF THE GENERATOR IS TO BE A PART OF THIS PERMIT, SPEC | | | SHEETS ON THE GENERATOR SHALL BE SUBMITTED ACCOMPANIED | | | BY LOAD CALCS FOR THE GENERATOR CONNECTED LOADS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|