2015-09-23 18:49:41PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 PG. E.1
 1. YOU ARE MISSING EMERGENCY LIGHTING IN: THE
 ELECTRICAL ROOM, THE REST ROOMS MECHANICAL ROOM,
 GALLERY STAIRS AND ART WAREHOUSE.
 2. THERE IS A MISSING EXIT LIGHT IN ROOM 211 TOWARDS
 THE REAR STAIRS.
 PG. E.2
 1. YOU SHALL ADHERE TO THE MANDATORY LIGHTING CONTROL
 REQUIREMENTS OF THE 2014 FBC-ENERGY SECTION 505
  
 IF THE GENERATOR IS TO BE A PART OF THIS PERMIT, SPEC
 SHEETS ON THE GENERATOR SHALL BE SUBMITTED ACCOMPANIED
 BY LOAD CALCS FOR THE GENERATOR CONNECTED LOADS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  