2015-09-09 08:25:28BUILDING PLAN REVIEW
 W.P.B. PERMIT:15081109- MASTER
 W. P. B. PERMIT: 15081111-FOUNDATION
 ADD: 444 BUNKER RANCH RD.
 CONT: CURY BUILDING & DESIGN
 TEL: (561)718-1398
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 09/2015
 ACTION: DENIED
  
 CONTRACTOR TO BIND ALL PLANS INTO A SET, CIVIL, SURVEY
 AND CIVIL, ARCHITECTURAL, STRUCTURAL, MECHANICAL,
 ELECTRICAL & PLUMBING COMBINED TO MAKE ONE SET. AS
 SUBMITTED IT LOOKS LIKE 4 SETS OF CIVIL WERE SUBMITTED.
 AS PLAN REVIEWERS WE USUALLY LOOK ONLY AT ONESET OF
 PLANS. WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) SHEET S07 CODE REFERENCE SHEET. LIST THE 2014, 5TH
 EDITION OF THE FLORIDA BUILDING CODE. THE PLANS ARE
 SILENT TO WHAT DESIGN THE PLANS WERE DESIGN TO UNDER
 THE 2014 FBC-EXISTING BUILDING CODE, 301.1.
  
 2) SHEET S07 STUCTURAL NOTES UNDER THE HEADING OF
 MATERIALS THE STRENGTH OF CONCRETE IS DECLARED FOR
 SLABS, COLUMNS AND BEAMS, SHEET S02 THE COLUMN SCHEDULE
 UNIT C6 IS FILLED CELL MASONRY THE PLANS INDICATE THE
 USE OF 3000 PSI CONCRETE, IN FILED CELL MASONRY
 SHOULDN'T THE USE OF GROUT BE USED INSTEAD OF CONCRETE.
 ACI 530 1.16.1. & TABLE 1.16.1 GROUTING MINIMUM SPACES.
  
 3) SHEET S2 FOOTING SCHEDULE FOOTING F2-F6 INDICATES
 THE WIDTH & LENGTH OF THE FOOTING BUT NOT THE HEIGTH.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET S2 FOOTING SCHEDULE F4 DOES NOT PROVIDE AT
 WHAT CENTER TO CENTER IN INCHES WHAT THE STEEL MATS ARE
 TO BE INSTALLED. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 5) SHEET S-7 INDICATES THE PLANS WERE DESIGNED TO THE
 2014 FBC-B AND ASCE 7-10. THE WIND DESIGN CRITERIA IS
 NOT PROVIDED. 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCERESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 5.2. RISK CATEGORY.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE
 STRUCTURE, PSF (KN/M2).
  
 6) SHEET S7 & S1. PROVIDE THE MEAN ROOF HEIGTH AND
 SECTION THROUGH THE ROOF WITH ELEVATION OF ROOF AND OF
 THE PARAPET. THE MEAN ROOF HEIGHT CAN NOT BE DETERMINED
 , NOR CAN THE PRESSURES FOR WINDOWS AND DOORS . 2014
 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS FOR BUILDING
 HEIGHT AND EXPOSURE.
  
 7) SHEET S7 & S4. PROVIDE THE MEAN ROOF HEIGTH AND
 SECTION THROUGH THE ROOF WITH ELEVATION OF ROOF AND OF
 THE PARAPET. THE MEAN ROOF HEIGHT CAN NOT BE DETERMINED
 , NOR CAN THE PRESSURES FOR ROOF ZONES, NOTE THE
 PRESSURES ARE ASSUMED TO BE VASD? 2014 FBC-B TABLE
 1609.7(2) ADJUSTMENT FACTORS FOR BUILDING HEIGHT AND
 EXPOSURE.
  
 8) MISSING PRODUCT APPROVALS: 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS FOR EXHAUST
 FANS AND A/C ROOF TOP DOWN UNITS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 9A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9B) EITHER THE CONTRACTOR OR DESIGN PROFESSIONAL CAN
 ELECT TO DEFER THE PRODUCT APPROVALS TO AFTER PERMIT
 ISSUANCE, IF SO PLEASE PROVIDE A WRITTEN RESPONSE.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 10) THERE ARE NO A SHEETS, MECHANICAL NO FP SHEETS
 SHOWING THE ROOF DECK, THE M2 SHEET SHOWS A COMMERCIAL
 GAS STOVE AND S4 INDICATES THE KITCHEN HOOD EXHAUST BY
 OTHER. SHEET S6 DETAIL # 4 SHOWS A NEW ROOF TOP ACCESS
 WITH ROOF TOP DOOR.
  
 10A) SHEET S3 ROOF FRAMING PLANDOES NOT PROVIDE A
 SECTION FOR THE ROOF FRAMNG AND HEADER FOR THE NEW
 EXHAUST VENT THAT WILL GO THROUGH THE ROOF FRAMING AND
 SHEATHING. NOTE THERE IS ALSO NO ROOF TOP CURB DETAIL,
 HOW IT IS TO BE ANCHORED TO THE ROOF FRAMING.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 10B) WITH THE LOCATION OF THE EXHAUST FAN NOT PROVIDED
 NOR THE HEIGHT OF THE PARAPET PLEASE SHOW COMPLIANCE
 WITH 2014 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS
 SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS,
 ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE
 SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF
 EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR
 OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL EXTEND NOT
 LESS THAN 30 INCHES (762 MM) BEYOND EACH END OF SUCH
 APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE THE
 ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 MM)
 OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND
 SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES
 (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE
 OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 10C) PLEASE REVIEW THE REQUIREMENTS FOR SCREENS FOR
 MECHANICAL EQUIPMENT. 1509.6 MECHANICAL EQUIPMENT
 SCREENS. MECHANICAL EQUIPMENT SCREENS SHALL BE
 CONSTRUCTED OF THE MATERIALS SPECIFIED FOR THE EXTERIOR
 WALLS IN ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF
 THE BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS
 GREATER THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT
 SCREENS SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 11) SHEET L1 & L2 WHAT APPEARS TO BE FIRE RATED
 VERTICAL EXIT STAIRS NEITHER LIFE SAFETY SHEET DO NOT
 PROVIDE WALL IDENTIFICATION TAGS SHOWING THE TYPE OF
 WALL OR IF FIRE RATINGS, MISSING UL LISTING OF STAIR
 ENCLOSUE. 2014 FBC-B 1023.3 CONSTRUCTION. 1023.6
 PENETRATIONS. GAURDS
  
 12) SHEET L1 & L2 THERE IS NO DOOR SCHEDULE TO BE ABLE
 TO IDENTIFY DOOR OPENINGS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. 107.3.5.1.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
  
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 CONSTRUCTION REQUIREMENTS
  
 13) PLEASE PROVIDE DETAILS FOR THE ACCESSIBLE RESTROOMS
 SHOW COMPLIANCE WITH 107.3.5.1.1 MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS. ACCESSIBILITY
 REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 VERTICAL ACCESSIBILITY 2014 FL ACCESS CODE SECTION 407
 ELEVATOR
 TOILET AND BATHING FACILITIES 2014 FL ACCESS CODE
 CHAPTER 6
 DRINKING FOUNTAINS 2014 FL ACCESS CODE 602
 SINKS -BREAK ROOM AREAS. 2014 FL ACCESS CODE 606.(1-5).
  
 14) SHEET LS2 INDICATES A THEATER IN ROOM 210 PLEASE
 PROVIDE ADDITIONAL DETAILS, SEAT LAYOUT, STADIUM STYE
 RAISED TIERS? ADDITIONAL INFORMATION IS REQUIRED FOR
 CODE COMPLIANCE.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  