2015-10-27 15:19:262ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15081103
 10/27/15
  
 1) THE REQUESTED SIZING CALCULATIONS FOR THE DAIKIN AC
 SYSTEM WERE NOT PROVIDED. IN RESPONSE TO THE COMMENT,
 THE DESIGN PROFESSSION IS INDICATING EQUIPMENT CUT
 SHEETS WERE USED TO ESTABLISH THE HEAT LOAD- PLEASE
 PROVIDE THE CUT SHEETS AS INDICATED.
 2) SHEET M02.00: REMOVE OR REVISE THE UNDERFLOOR
 EQUIPMENT SCHEDULE. THE UNDERFLOOR HEATERS HAVE BEEN
 REPLACED WITH ABOVE CEILING UNITS.
 3) PROVIDE SIZING CALCULATIONS FOR THE NEW ABOVE
 CEILING HEATERS IN COMPLIANCE WITH SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 4) PROVIDE SUPPORT AND CONNECTION DETAILS FOR
 INSTALLATION OF THE ABOVE CEILING HEATERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER