| Plan Review Notes For Permit 15081103 |
| Permit Number |
15081103 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-27 15:19:26 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15081103 | | | 10/27/15 | | | | | | 1) THE REQUESTED SIZING CALCULATIONS FOR THE DAIKIN AC | | | SYSTEM WERE NOT PROVIDED. IN RESPONSE TO THE COMMENT, | | | THE DESIGN PROFESSSION IS INDICATING EQUIPMENT CUT | | | SHEETS WERE USED TO ESTABLISH THE HEAT LOAD- PLEASE | | | PROVIDE THE CUT SHEETS AS INDICATED. | | | 2) SHEET M02.00: REMOVE OR REVISE THE UNDERFLOOR | | | EQUIPMENT SCHEDULE. THE UNDERFLOOR HEATERS HAVE BEEN | | | REPLACED WITH ABOVE CEILING UNITS. | | | 3) PROVIDE SIZING CALCULATIONS FOR THE NEW ABOVE | | | CEILING HEATERS IN COMPLIANCE WITH SECTION C403.2.1 | | | FBC-14 ENERGY CONSERVATION. | | | 4) PROVIDE SUPPORT AND CONNECTION DETAILS FOR | | | INSTALLATION OF THE ABOVE CEILING HEATERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|