| Notes |
| Date |
Text |
| 2015-10-29 13:40:54 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION | | | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION | | | OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND | | | BELOW ARE THE DEFICIENCIES NOTED. | | | | | | THOUGH THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | | ADDRESSED, THE NEW PLANS HAVE A COUPLE OF ITEMS NEEDING | | | CORRECTION: | | | 1. PANEL H3 DOES NOT APPEAR ON THE RISER DIAGRAM AS | | | SUCH, IT IS MISLABELED AS HP3. CORRECT TO MATCH. | | | 2. THE RISER DIAGRAM REFLECTS A PANEL L3C, BUT THERE IS | | | NOT PANEL SCHEDULE FOR IT ON THE NEW PLANS. | | | | | | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN | | | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED | | | FOR ANOTHER REVIEW. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE | | | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | . | | | |
|