| Plan Review Notes For Permit 15081103 |
| Permit Number |
15081103 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-02 12:14:58 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF | | | THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH | | | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE | | | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED | | | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. | | | 1. FIRE ALARM WORK SHALL BE PERFORMED UNDER SEPARATE | | | PERMIT. | | | 2. MISSING EXIT LIGHT ON OPPOSITE SIDE OF THE OPEN AREA | | | CORRIDOR. | | | 3. CORRECT FIXTURE SCHEDULE TO C-EM TYPE TO INCLUDE THE | | | BATTERY PACK. | | | 4. PROVIDE CIRCUIT DIRECTORY FOR THE ODD SIDE OF PANEL | | | L3A. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|