| 2015-09-26 14:48:00 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15081103 |
| | ADD: 1641 WORTHINGTON RD. SUITE # ????? |
| | CONT: TBD |
| | TEL: (954)993-4742 / STEVE MORIN |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. SEPT. 26/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) NEITHER THE PERMIT APPLICATION NOR THE PLANS PROVIDE |
| | WHAT THE SUITE NUMBER IS GOING TO BE FOR THIS TENANT. |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107.2.1. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | WHERE WORK IS TO BE PREFORMED. |
| | 2014 FBC-B 501.2 ADDRESS IDENTIFICATION. |
| | |
| | 2) PLEASE PROVIDE THE TOTAL SQUARE FOOTAGE OF THE LARGE |
| | MEETING ROOM 03K06, THE HUDDLE ROOM 03K09, MEDIUM |
| | MEETING ROOM 03K09, |
| | THE BOARD ROOM 03E13 AND THE PANTRY ROOM NUMBER 03B13. |
| | IT APPEARS ALL OF THESE ROOMS ARE MEETING ROOMS AND THE |
| | COMBINED SQUARE FOOTAGE THEY WOULD BE CLASSIFIED AS |
| | ASSEMBLY. THIS MAY BE CONSIDERED A MIXED OCCUPANCY |
| | BETWEEN A3 ASSEMBLY AND BUSINESS OCCUPANCY. PLEASE |
| | PROVIDE THE TOTAL SQ. FOOTAGE FOR THIS FLOOR NOT TENANT |
| | SPACE, IF THE ASSEMBLY OCCUPANCY SQUARE FOOTAGE IS MORE |
| | THAN 10 PER CENT OF THE FLOOR AREA FOR THE BUILDING |
| | INCLUSIVE OF ALL ASSEMBLY AREAS ON THIS FLOOR, THEN IT |
| | IS A MIXED OCCUPANCY AND THE DESIGNER OF RECORD WILL |
| | NEED TO INDICATE COMPLIANCE WITH EITHER 508.3 |
| | NONSEPARATED OCCUPANCIES OR 508.4 SEPARATION OF |
| | OCCUPANCIES. |
| | |
| | 3) SHEET M01.01 NOTE # 8 INDICATES NEW REFRIGARANT |
| | LINES ARE GOING TO BE INSTALLED UP THROUGH THE ROOF. |
| | WHAT THIS PLAN DOES NOT PROVIDE IS HOW THESE LINES ARE |
| | GOING TO BE RUN. SHEET A02.03 INDICATES THE WALL TYPE |
| | AS DB3. ON SHEET A12.00 THIS IS NOT A RATED WALL THE |
| | ACTUAL RATED STAIR ENCLOSURE WALL IS A SEPARATE AND |
| | SHOWING AS RATED. THE UNKNOWN IS THIS A SHAFT WALL, |
| | CHASE PLEASE PROVIDE MORE DETAIL IN THIS AREA HOW CODE |
| | COMPLIANCE WILL BE MET. IS THERE ANOTHER FLOOR ON TOP |
| | OF THIS FLOOR IF SO HOW WILL THE PENETRATION BE SEALED. |
| | 2014 FBC-B 717.6.1 THROUGH PENETRATIONS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |