| 2015-09-02 15:04:56 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE |
| | ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN |
| | FOR INSPECTION. NO SITE TUBES WILL BE ALLOWED. IF |
| | DIRECT BORING, HAVE THE CERTIFICATE OF COVER AVAILABLE |
| | FOR THE INSPECTOR. (THIS CAN BE ADDRESSED WITH A NOTE |
| | ON THE CORRECTED PLANS.) |
| | 2. NEC 210.63 REQUIRES THAT THERE BE A SERVICE OUTLET |
| | WITHIN 25 FEET OF THE HVAC UNIT. INCLUDE THAT ON THE |
| | NEW RESIDED DRAWINGS. |
| | 3. ALL WIRING SHALL BE REMOVED FROM EVERY ABANDONED |
| | OUTLET AS PRESCRIBED IN NEC 372.13. |
| | 4. THE REMAINS OF THE FEEDER RACEWAY TO PANEL "L35" |
| | SHALL BE SEALED AT BOTH ENDS. |
| | 5. YOUR RISER DIAGRAM REFLECTS TWO METERS FOR PANEL |
| | "L35" CORRECT ACCORDINGLY. |
| | 6. PROVIDE SITE SPECIFIC LOAD CALCS AND PANEL SCHEDULES |
| | FOR PANELS "L35" & "L1" |
| | 7. NEW EXHAUST FANS APPEAR TO BE 2 POLE, YET THE |
| | CIRCUIT SCHEDULE FOR PANEL A REFLECTS A SINGLE CKT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |