| 2015-12-20 10:18:12 | 1) 1) SUBMIT A WATER RISER DIAGRAM FOR THE WATER | | | CLOSET, LAVATORY & EMERGENCY EYE-WASH / SHOWER FOR | | | REVIEW. WPB AMEND. TO FBC SEC. 107.3.5.1.3. 2ND | | | REQUEST. THE SUBMITTED DIAGRAM IS A SANITARY RISER, NOT | | | A WATER RISER. | | | 2) THE GENERATOR SPECS. REFLECT A 1,000 GALLON SUB-BASE | | | FUEL TANK BUT SPECIFICATIONS HAVE ALSO BEEN SUBMITTED | | | FOR A DOUBLE WALL SECONDARY CONTAINMENT TANK. CLARIFY. | | | 3) SUBMIT DETAILS FOR THE DEADMEN. NOTE #5 ON SHT. C-4 | | | NOTES THAT SHOP DRAWINGS & SIGNED & SEALED CALCULATIONS | | | TO BE DONE BY FL. REGISTERED ENGINEER TO BE SUBMITTED | | | BY CONTRACTOR. MANUFACTURER'S SPECIFICATIONS HAVE BEEN | | | SUBMITTED.THIS DOES NOT SATISFY NOTE #5. | | | 4) FUEL TANKS IN EXCESS OF 550 GALLONS REQUIRE THE | | | APPROVAL FROM PALM BEACH COUNTY DEPARTMENT OF | | | ENVIRONMENTAL RESOURCE MANAGEMENT PER COUNTY ORDINANCE | | | 2015-008 AND F.A.C. RULE 62-762.301. | | | 5) SUBMIT A FUEL OIL PIPING DIAGRAM IF NEW PIPING WILL | | | BE INSTALLED. SHOW TYPE OF PIPE, SIZES, ETC.WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|