Plan Review Notes
Plan Review Notes For Permit 15081084
Permit Number 15081084
Review Stop B
Sequence Number 2
Notes
Date Text
2016-01-04 09:54:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15081084
 ADD: 1801 @ PARKER AVE.
 CONT: TBD
 TEL: ( 561)494-1075
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 04 /2016
 ACTION: DENIED
  
 NOTE: GENERATOR AND FUEL TANK ARE UNDER SEPERATE
 PERMIT!!!!!!
  
 1) COMPLIED. PLANS DESIGNED TO THE 2014 FBC.
  
 2) SEMI- COMPLIED. ALTHOUGH THE FLOOD ELEVATION
 CERTIFICATE IS A FEDERAL FORM AND STATES THAT SURVEYOR,
 ENGINEERS AND OR ARCHITECTS AUTHORIZED BY LAW TO
 CERTIFY ELEVATION INFORMATION, FLORIDA STATE STATUTES
 472.005(3),(4A-4B) ONLY FLORIDA LICENSED SURVEYOR CAN
 FILE OUT THIS FORM.
 THE PERMIT APPLICATION ADDRESS INDICATES THIS STRUCTURE
 IS BUILT IN AN A9 FLOOD ZONE THE BASE ELEVATION 13 FEET
 AND THE CITY REQUIRES AN ADDTIONAL 6 INCH FREEBOARD OR
 MINIMUM OF 13 FT. 6 INCHES. FBC BUILDING 1612 AND CITY
 OF WPB CODE OF ORDINANCES SECTION 94-546.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) 2ND REQUEST. NOTE THE SUBMITTED SOILS REPORT IS A
 COPY OF THE ORIGINAL SIGNATURE NOT THE ORIGINAL. THE
 SECOND ISSUE WITH THE SOILS REPORT THE DOCUMENT IS NOT
 SEALED. THE COVER SHEET DOES NOT LIST HOW MANY PAGES
 ARE UNDER THE SOILS ENGINEER SEAL, NOR IS THERE A
 SEALED INDEX SHEET INDICATING HOW MANY PAGES ARE
 COVERED UNDER THE ENGINEERS SUPPOSED SEAL. THERE ARE
 TWO ENGINEERS NAMES ON THE REPORT, SIGNED, PRINTED AND
 LICENSE NUMBERS, THERE IS NO DOCUMENTATION AS TO WHAT
 PART OF THE SOILS REPORT EACH IS RESPONSIBLE FOR.
  
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS. WHEN ELEMENTS OF THE PROJECT ARE
 SHOWN ON AN ENGINEERING DOCUMENT ONLY FOR INFORMATION
 OR CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 SHEET S1 UNDER THE HEADING OF SLAB ON GRADE SOILS
 REPORTS ARE REQUIRED. 2014 FBC-B 1803.5.2 QUESTIONABLE
 SOILS, SOILS GEOTECHNICAL REPORT REQUIRED. SHEET S3
 INDICATES THE INSTALATION OF 20 FOOT STEEL SHEET PILE.
  
 4-6) COMPLIED.
  
 7) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SWING AND OVERHEAD TYPE
 (C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES-
  
 FL 7473-R6 EAGLE ROOFING TILE: ON SHEETS 2 & 3 OF THE
 APPROVAL, THE TILE TYPE WAS NOT IDENTIFIED.
  
 SHEET 3 OF 4, LIMITATION # 5.4 NOT COMPLIED. NO PRODUCT
 APPROVAL WAS SUBMITTED. UNDERLAYMENT SHALL BE THAT
 APPROVED BY EAGLE ROOFING PRODUCTS, LLC, WHICH HOLDS
 FLORIDA PRODUCT APPROVAL FOR USE WITH TILE ROOFING
 SYSTEMS. THE UNDERLAYMENT PRODUCT APPROVAL SHALL
 SPECIFY ALLOWABLE METHOD(S) OF TILE INSTALLATION
 (MECHANICAL ATTACHMENT, MORTAR-SET AND/OR ADHESIVE-SET)
 FOR USE WITH THE SPECIFIC UNDERLAYMENT. FOR MORTAR-SET
 OR ADHESIVE-SET TILE ROOFING APPLICATIONS, THE
 UNDERLAYMENT PRODUCT APPROVAL SHALL SPECIFY ATTACHMENT
 METHODS FOR THE UNDERLAYMENT SYSTEM TO RESIST WIND
 UPLIFT DESIGN LOADS IN ACCORDANCE WITH TABLE 1A OF
 FRSA/TRI APRIL 2012 (04-12).
  
 FRSA/ TRI TABLE IA THE WRONG EXPOSURE AND WIND SPEED IS
 INDENTIFIED AND NO MEAN ROOF HEIGHT GIVEN. EXPOSURE C/
 180 MPH( BUILD CAT. IV) MEAN ROOF HEIGHT OF 15 FEET.
  
 8) 2ND REQUEST. RESPONSE INDICATES THAT CLOSE
 CONSTRUCTION TO RESPOND/ SUPPLY INFORMATION. 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) 2ND REQUEST. SHEET S-3, S-4,S6, S7 & S9 ALL SHOW
 DETAILS OF THE NEW HIPPED TRUSS ROOF SYSTEM ON TOP OF A
 CONCRETE SLABBED ROOF SYSTEM. NOTE THE PLANS INDICATE A
 (2) POINT ANCHOR LOCATION FOR THE TRUSSES. THE AREA OF
 CONCERN IS THE 4 FOOT AND 6 FOOT TRUSS TAILS WITH NO
 ANCHOR SYSTEM FOR UPLIFT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. ON THE 1ST REVIEW THE 2 POINTS
 OF ANCHORING WERE SHOWN, THE ISSUE IS WITHOUT THE
 ENGINEERED TRUSS SHEETS THE UPLIFT LOADS FOR THE 4 FOOT
 AND 6 FOOT OVER- HANGS ARE UNKNOWN.
  
 10) 2ND REQUEST. PLEASE PROVIDE TYPE OF APPROVED
 ADHESIVE? SHEET S-6 & S-7 BOTH SHOW NEW DECROTIVE
 OUTRIGGERS OF 8 INCHES IN HEIGHT, THE PLANS DO NOT
 PROVIDE THE WIDTH OF THE OUTRIGGERS, NOR DO THEY
 SPECIFY GRADE OR SPECIES OF WOOD THEY ARE TO BE MADE
 FROM. THE PLANS DO NOT INDICATE HOW THEY ARE TO BE
 ANCHORED TO THE NEW CONCRETE DECK NOR HOW THEY WILL BE
 ANCHORED TO THE EXISITNG SLOPED CONCRETE DECKS?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 11) 2ND REQUEST. ADDITIONAL INFORMATION IS REQUIRED
 SINCE THE EXPOSURE AND WIND SPEED WAS INCORRECT. SHEET
 S-8 DETAIL # 4 SHOWS A HIP AND RIDGE DETAIL WITH WOOD
 2X FOR ANCHORING OF HIP AND RIDGE TILE. THE PLANS DO
 NOT INDICATE HOW THE RIDGE BOARD IS TO BE ATTACHED.
 SHOW COMPLIANCE WITH 2014 FBC-B 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY ROOF TILE
 INSTALLATION MANUAL, FIFTH EDITION WHERE THE BASIC WIND
 SPEED, VASD, IS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  