| Plan Review Notes For Permit 15081084 |
| Permit Number |
15081084 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-05 11:43:00 | 1) SUBMIT A WATER RISER DIAGRAM FOR THE WATER CLOSET, | | | LAVATORY & EMERGENCY EYE-WASH / SHOWER FOR REVIEW. WPB | | | AMEND. TO FBC SEC. 107.3.5.1.3. | | | 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS | | | FOR THE NEW GENERATOR.SHT. C-1 NOTE B READS "SEE SPECS | | | FOR NEW GENERATOR". THERE ARE NO GENERATOR SPECS IN | | | THIS SUBMITTAL. WHAT TYPE OF FUEL POWERS THE GENERATOR? | | | WPB AMEND. TO FBC SEC. 107.1. | | | 3) SUBMIT SPECIFICATIONS FOR THE WASTEWATER TANK | | | TIE-DOWNS. THE TABLE ON C-4 ONLY SHOWS THE NUMBER OF | | | STRAPS. SHOW WHERE ARE THE STRAPS TO BE LOCATED ON THE | | | TANK, THE DISTANCE BETWEEN THE STRAPS, THE TYPE, WIDTH, | | | AND ANCHORING DETAILS AS TO HOW THE STRAPS WILL BE | | | ANCHORED TO THE DEADMEN TO PROVIDE PROTECTION AGAINST | | | FLOTATION FORCES.. | | | 4) SUBMIT DETAILS FOR THE DEADMEN. SHT. C-4 NOTES THAT | | | SHOP DRAWINGS/ SIGNED & SEALED CALCULATIONS TO BE DONE | | | BY FL. REGISTERED ENGINEER TO BE SUBMITTED BY | | | CONTRACTOR. THIS CAN BE DONE AS A DEFERRED SUBMITTAL. | | | 5) SHT. S-3 NOTE #3 - PVC CANNOT BE USED FOR WATER | | | DISTRIBUTION. PIPE MATERIAL FOR WATER DISTRIBUTION | | | SHALL COMPLY WITH 2014 FBC-PLUMBING, TABLE 605.4. PVC | | | CAN BE USED FOR THE WATER SERVICE FROM THE METER TO THE | | | BUILDING. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|