Plan Review Notes
Plan Review Notes For Permit 15081084
Permit Number 15081084
Review Stop P
Sequence Number 1
Notes
Date Text
2015-09-05 11:43:001) SUBMIT A WATER RISER DIAGRAM FOR THE WATER CLOSET,
 LAVATORY & EMERGENCY EYE-WASH / SHOWER FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE NEW GENERATOR.SHT. C-1 NOTE B READS "SEE SPECS
 FOR NEW GENERATOR". THERE ARE NO GENERATOR SPECS IN
 THIS SUBMITTAL. WHAT TYPE OF FUEL POWERS THE GENERATOR?
 WPB AMEND. TO FBC SEC. 107.1.
 3) SUBMIT SPECIFICATIONS FOR THE WASTEWATER TANK
 TIE-DOWNS. THE TABLE ON C-4 ONLY SHOWS THE NUMBER OF
 STRAPS. SHOW WHERE ARE THE STRAPS TO BE LOCATED ON THE
 TANK, THE DISTANCE BETWEEN THE STRAPS, THE TYPE, WIDTH,
 AND ANCHORING DETAILS AS TO HOW THE STRAPS WILL BE
 ANCHORED TO THE DEADMEN TO PROVIDE PROTECTION AGAINST
 FLOTATION FORCES..
 4) SUBMIT DETAILS FOR THE DEADMEN. SHT. C-4 NOTES THAT
 SHOP DRAWINGS/ SIGNED & SEALED CALCULATIONS TO BE DONE
 BY FL. REGISTERED ENGINEER TO BE SUBMITTED BY
 CONTRACTOR. THIS CAN BE DONE AS A DEFERRED SUBMITTAL.
 5) SHT. S-3 NOTE #3 - PVC CANNOT BE USED FOR WATER
 DISTRIBUTION. PIPE MATERIAL FOR WATER DISTRIBUTION
 SHALL COMPLY WITH 2014 FBC-PLUMBING, TABLE 605.4. PVC
 CAN BE USED FOR THE WATER SERVICE FROM THE METER TO THE
 BUILDING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  