| Plan Review Notes For Permit 15081084 |
| Permit Number |
15081084 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-08 14:14:39 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15081084 | | | 9/8/15 | | | | | | 1) AC COOLING AND HEATING CALCULATIONS, AND ENERGY | | | CALCULATIONS FOR A PROJECT AT 444 BUNKER RD. HAVE BEEN | | | SUBMITTED, HOWEVER THIS PROJECT IS AT 1801 PARKER AVE.( | | | AS LISTED ON THE PERMIT APPLICATION), AND 1700-1799 | | | PARKER AVE. (AS LISTED ON THE PLANS). PLEASE SUBMIT THE | | | CORRECT CALCULATIONS FOR THIS PROJECT. | | | 2) SUBMIT TWO COPIES OF A FLORIDA PRODUCT APPROVAL OR | | | MIAMI-DADE NOA FOR THE LOUVER- REFER TO SECTION | | | 1609.1.2 FBC-14 BUILDING, AND FL. DEPT. OF COMMUNITY | | | AFFAIRS RULE 9N-3. | | | 3) CLARIFY HOW THE VENTILATION OPENING IN THE PUMP ROOM | | | WAS SIZED- PROVIDE A CALCULATION, AND CLARIFY IF AN | | | EXHAUST FAN WILL BE INSTALLED TO MOVE THE VENTILATION | | | AIR THROUGH THE BUILDING- REFER TO SECTION 403 FBC-14 | | | MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|