Plan Review Notes
Plan Review Notes For Permit 15081084
Permit Number 15081084
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-08 14:14:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15081084
 9/8/15
  
 1) AC COOLING AND HEATING CALCULATIONS, AND ENERGY
 CALCULATIONS FOR A PROJECT AT 444 BUNKER RD. HAVE BEEN
 SUBMITTED, HOWEVER THIS PROJECT IS AT 1801 PARKER AVE.(
 AS LISTED ON THE PERMIT APPLICATION), AND 1700-1799
 PARKER AVE. (AS LISTED ON THE PLANS). PLEASE SUBMIT THE
 CORRECT CALCULATIONS FOR THIS PROJECT.
 2) SUBMIT TWO COPIES OF A FLORIDA PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE LOUVER- REFER TO SECTION
 1609.1.2 FBC-14 BUILDING, AND FL. DEPT. OF COMMUNITY
 AFFAIRS RULE 9N-3.
 3) CLARIFY HOW THE VENTILATION OPENING IN THE PUMP ROOM
 WAS SIZED- PROVIDE A CALCULATION, AND CLARIFY IF AN
 EXHAUST FAN WILL BE INSTALLED TO MOVE THE VENTILATION
 AIR THROUGH THE BUILDING- REFER TO SECTION 403 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719