2015-11-04 15:50:08THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. REGARDLESS OF WHEN THESE PLANS WERE DRAWN AND
 SEALED, THEY WERE SUBMITTED FOR PERMITTING AFTER THE
 2014 FBC TOOK EFFECT. THEREFORE ALL THE PLANS SHALL BE
 REVISED TO COMPLY WITH SAME.
 2. FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 3. CORRECT YOUR LOAD TABULATION. I GET 896 AMP.
 4. TOILET/WATER CLOSET IS MISSING THE REQUIRED LIGHTING
 AND SWITCH.
 5. ALL LIGHTING SHALL COMPLY WITH THE 5TH EDITION OF
 THE 2014 FBC-ENERGY CONSERVATION CODE.
 6. PROVIDE MANUFACTURER'S DATA SHEETS FOR PROPOSED
 GENERATOR.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  