| Plan Review Notes For Permit 15081057 |
| Permit Number |
15081057 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-27 16:45:22 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | | | | | | | COMMENTS: | | | 1.THE CLAIMED VALUATION OF THE PROJECT APPEARS TO BE | | | UNDERESTIMATED .PLEASE PROVIDE A SIGNED CONTRACT OR | | | PROPOSAL. | | | PER WPB AMEND. SEC 109.3 | | | 2.PROVIDE DRAWINGS THAT ARE LEDGABLE AND DRAWN TO 1/8 | | | IN. SCALE. | | | PER WPB AMEND. SEC 107.2.1 AND 107.2.1.4 | | | 3.PROVIDE FLOOR PLAN WITH EXISTING HOUSE AND LAYOUT OF | | | NEW BATHROOM. | | | PER WPB AMEND. SEC 107.2.1 | | | 4.ON ORIGINAL DRAWINGS NO BATHROOM IS SHOWN MASTER | | | PERMIT 14120197 SHOWS ONLY A STORAGE ROOM. A REVISION | | | IS NEEDED SHOWING NEW BATHROOM LAYOUT WITH ELICTRICAL , | | | PLUMBING AND STRUCTAUL, ALSO THE ORIGINAL SHOWS NO AC | | | IF NONE IT SHALL BE NOTED ON PLAN. | | | PER WPB AMEND. SEC 107.2.1 |
|